background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9668  P. 1 / 5

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

DC voltage input module ....................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures. 

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside a panel.
• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures* to ensure the CE con-
formity.
* For example, installation of noise filters and clamp fil-

ters for the power source, input and output connected 
to the unit, etc.

 

GENERAL PRECAUTIONS

• Before you remove or mount the unit, turn off the power 

supply and input signal for safety.

• Do not touch the connector while the power is supplied. 

Static electricity may cause a malfunction.

• Switches on the side of the module can be set for mainte-

nance only while the power supply is off.  Do not access 
them while the power is supplied.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

 

HOW TO MOUNT THE MODULE ON DIN RAIL

• I/O Module

Confirm that the locking clamps of the I/O module are set.
Insert the module in parallel to the next one while aligning the grooves of 
both modules (A & B in the above figure).
Maintain it perpendicularly to the rail. 

More I/O modules can be added in the same manner.

A

B

DC VOLTAGE INPUT MODULE

(8 points, isolated, tension clamp terminal block)

MODEL

R8-SVT8

Содержание R8-SVT8

Страница 1: ...the power supply and input signal for safety Do not touch the connector while the power is supplied Static electricity may cause a malfunction Switches on the side of the module can be set for mainte nance only while the power supply is off Do not access them while the power is supplied ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper ...

Страница 2: ...d slide it straight until the hooks are latched When removing the cover pull it out while squeezing the hooks inward Groove Hook HOW TO UNMOUNT THE MODULE ON DIN RAIL Release the locking clamps and pull out straight the module Caution 1 Be careful not to hurt your hand by pointed edges of the internal bus connector 2 I O modules cannot hold tightly on the DIN rail by themselves without power netwo...

Страница 3: ...nput 4 9 In5 Input 5 10 Input 5 11 In6 Input 6 12 Input 6 13 In7 Input 7 14 Input 7 15 In8 Input 8 16 Input 8 MODULE ADDRESS SW1 SW1 1 through 1 4 determine the tenth place digit while SW1 5 through 1 8 do the ones place digit of the module address Address is selected between 0 to 28 Factory setting 0 MODULE ADDRESS SW1 10 1 2 3 4 1 5 6 7 8 0 OFF OFF OFF OFF 1 OFF OFF OFF ON 2 OFF OFF ON OFF 3 OFF...

Страница 4: ... to 20 00 mA 20 00 mA Fine zero adjustment 320 00 to 320 00 0 00 Fine gain adjustment 3 2000 to 3 2000 1 0000 Scaled range Zero 32000 to 32000 0 Scaled range Span 32000 to 32000 10000 CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Loss of internal bus communication detection time 0 0 to 99 9 sec 1 0 sec Input moving average Disable Enable 8 times Disable Configuration mode DIP switc...

Страница 5: ... CONNECTOR EXC SUPPLY 1 INTERNAL POWER 1 Not used WIRING INSTRUCTIONS TENSION CLAMP TERMINAL BLOCK Unit side connector MC1 5 16 GF 3 5 Phoenix Contact Cable side connector FMC1 5 16 STF 3 5 Phoenix Contact Applicable wire size 0 2 1 5 mm2 Stripped length 10 mm Recommended solderless terminal AI0 25 10YE 0 25 mm2 Phoenix Contact AI0 34 10TQ 0 34 mm2 Phoenix Contact AI0 5 10WH 0 5 mm2 Phoenix Contac...

Отзывы: