R8-SVT8
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-9668 P. 3 / 5
COMPONENT IDENTIFICATION
■
FRONT VIEW
■
SIDE VIEW
AI_V
1
16
Input Connector
Internal Bus Connector
Function Setting
DIP SW
8
7
6
5
4
3
2
1
SW1
SW2
On
RUN
Status Indicator LED
Input Status Indicator LED
1
2
3
4
5
6
7
8
■
INDICATOR LED
ID
OPERATION
FUNCTION
Status
OFF
Stopping
Green ON
Valid host communication
Green Blinking
Reading/writing configuration
Red ON
Setting error
Red Blinking
Parameter error
Input
Status
OFF
Input data in the range
Red Blinking
Input data out of range
■
INPUT CONNECTOR ASSIGNMENT
1
16
PIN No.
ID
FUNCTION
1
In1
Input 1 (+)
2
Input 1 (–)
3
In2
Input 2 (+)
4
Input 2 (–)
5
In3
Input 3 (+)
6
Input 3 (–)
7
In4
Input 4 (+)
8
Input 4 (–)
9
In5
Input 5 (+)
10
Input 5 (–)
11
In6
Input 6 (+)
12
Input 6 (–)
13
In7
Input 7 (+)
14
Input 7 (–)
15
In8
Input 8 (+)
16
Input 8 (–)
■
MODULE ADDRESS: SW1
SW1-1 through 1-4 determine the tenth place digit, while
SW1-5 through 1-8 do the ones place digit of the module
address.
Address is selected between 0 to 28.
(Factory setting: 0)
MODULE ADDRESS
SW1
×10
1
2
3
4
×1
5
6
7
8
0
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
OFF
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
OFF
5
OFF
ON
OFF
ON
6
OFF
ON
ON
OFF
7
OFF
ON
ON
ON
8
ON
OFF
OFF
OFF
9
ON
OFF
OFF
ON
■
OPERATING MODE
(*) Factory setting
• Input Range: SW2-1, 2
Same setting for all channels. Use PC Configurator to set
independent ranges per channel.
INPUT RANGE
SW2
1
2
-10 - +10V DC (*)
OFF
OFF
0 - 10V DC
ON
OFF
0 - 5V DC
OFF
ON
1 - 5V DC
ON
ON
• Terminator DIP SW: SW2-6
TERMINATOR SW
SW2-6
Without (*)
OFF
With
ON
• Configuration Mode: SW2-8
CONFIGURATION MODE
SW2-8
DIP switch setting (*)
OFF
PC Configurator and communication
ON
Note: Be sure to set unused SW2-3 through 2-5 and 2-7 to
OFF.