background image

R8-SVT8

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9668  P. 3 / 5

COMPONENT IDENTIFICATION

 FRONT VIEW

 SIDE VIEW

AI_V

1

16

Input Connector

Internal Bus Connector

Function Setting

DIP SW

8

7

6

5

4

3

2

1

SW1

SW2

On

RUN

Status Indicator LED

Input Status Indicator LED

1

2

3

4

5

6

7

8

 

INDICATOR LED

ID

OPERATION

FUNCTION

Status

OFF

Stopping

Green ON

Valid host communication

Green Blinking

Reading/writing configuration

Red ON

Setting error

Red Blinking

Parameter error

Input
Status

OFF

Input data in the range

Red Blinking

Input data out of range

 

INPUT CONNECTOR ASSIGNMENT

1

16

PIN No.

ID

FUNCTION

1

In1

Input 1 (+)

2

Input 1 (–)

3

In2

Input 2 (+)

4

Input 2 (–)

5

In3

Input 3 (+)

6

Input 3 (–)

7

In4

Input 4 (+)

8

Input 4 (–)

9

In5

Input 5 (+)

10

Input 5 (–)

11

In6

Input 6 (+)

12

Input 6 (–)

13

In7

Input 7 (+)

14

Input 7 (–)

15

In8

Input 8 (+)

16

Input 8 (–)

 

MODULE ADDRESS: SW1

SW1-1 through 1-4 determine the tenth place digit, while 

SW1-5 through 1-8 do the ones place digit of the module 

address.

Address is selected between 0 to 28.

(Factory setting: 0)

MODULE ADDRESS

SW1

×10

1

2

3

4

×1

5

6

7

8

0

OFF

OFF

OFF

OFF

1

OFF

OFF

OFF

ON

2

OFF

OFF

ON

OFF

3

OFF

OFF

ON

ON

4

OFF

ON

OFF

OFF

5

OFF

ON

OFF

ON

6

OFF

ON

ON

OFF

7

OFF

ON

ON

ON

8

ON

OFF

OFF

OFF

9

ON

OFF

OFF

ON

 

OPERATING MODE

(*) Factory setting

• Input Range: SW2-1, 2

Same setting for all channels.  Use PC Configurator to set 

independent ranges per channel.

INPUT RANGE

SW2

1

2

-10 - +10V DC (*)

OFF

OFF

0 - 10V DC

ON

OFF

0 - 5V DC

OFF

ON

1 - 5V DC

ON

ON

• Terminator DIP SW: SW2-6

TERMINATOR SW

SW2-6

Without (*)

OFF

With

ON

• Configuration Mode: SW2-8

CONFIGURATION MODE

SW2-8

DIP switch setting (*)

OFF

PC Configurator and communication

ON

Note:  Be sure to set unused SW2-3 through 2-5 and 2-7 to 

OFF.

Содержание R8-SVT8

Страница 1: ...the power supply and input signal for safety Do not touch the connector while the power is supplied Static electricity may cause a malfunction Switches on the side of the module can be set for mainte nance only while the power supply is off Do not access them while the power is supplied ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper ...

Страница 2: ...d slide it straight until the hooks are latched When removing the cover pull it out while squeezing the hooks inward Groove Hook HOW TO UNMOUNT THE MODULE ON DIN RAIL Release the locking clamps and pull out straight the module Caution 1 Be careful not to hurt your hand by pointed edges of the internal bus connector 2 I O modules cannot hold tightly on the DIN rail by themselves without power netwo...

Страница 3: ...nput 4 9 In5 Input 5 10 Input 5 11 In6 Input 6 12 Input 6 13 In7 Input 7 14 Input 7 15 In8 Input 8 16 Input 8 MODULE ADDRESS SW1 SW1 1 through 1 4 determine the tenth place digit while SW1 5 through 1 8 do the ones place digit of the module address Address is selected between 0 to 28 Factory setting 0 MODULE ADDRESS SW1 10 1 2 3 4 1 5 6 7 8 0 OFF OFF OFF OFF 1 OFF OFF OFF ON 2 OFF OFF ON OFF 3 OFF...

Страница 4: ... to 20 00 mA 20 00 mA Fine zero adjustment 320 00 to 320 00 0 00 Fine gain adjustment 3 2000 to 3 2000 1 0000 Scaled range Zero 32000 to 32000 0 Scaled range Span 32000 to 32000 10000 CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Loss of internal bus communication detection time 0 0 to 99 9 sec 1 0 sec Input moving average Disable Enable 8 times Disable Configuration mode DIP switc...

Страница 5: ... CONNECTOR EXC SUPPLY 1 INTERNAL POWER 1 Not used WIRING INSTRUCTIONS TENSION CLAMP TERMINAL BLOCK Unit side connector MC1 5 16 GF 3 5 Phoenix Contact Cable side connector FMC1 5 16 STF 3 5 Phoenix Contact Applicable wire size 0 2 1 5 mm2 Stripped length 10 mm Recommended solderless terminal AI0 25 10YE 0 25 mm2 Phoenix Contact AI0 34 10TQ 0 34 mm2 Phoenix Contact AI0 5 10WH 0 5 mm2 Phoenix Contac...

Отзывы: