BEFORE USE ....

Thank you for choosing M-System.  Before use, check the 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Power/network module ....................................................(1)
Protective cover ...............................................................(1)

 

MODEL NO.

Confirm that the model number described on the product is 
exactly what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures. 

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside a panel.
• The actual installation environments such as panel con-

figurations, connected devices and connected wires may 
affect the protection level of this unit when it is integrat-
ed in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

 

GENERAL PRECAUTIONS

Before you remove or mount the unit, turn off the power 
supply.

 

POWER INPUT RATING & OPERATIONAL RANGE

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:

DC Power supply: 24V DC ±10%,

approx. 12W (@ output current 1.6 A)

Excitation supply: 24V DC ±10%,

operational current 10A

 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not apply physical impact to the unit.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

The unit is designed to function as soon as power is sup-
plied, however for analog module, a warm up for 10 minutes 
is required for satisfying complete performance described 
in the data sheet.

INSTALLATION

Internal power supply/communication is connected via each 
module’s connector, therefore no backplane base is required, 
however, hot-swapping of modules is not possible.

 

STATION ADDRESS & NETWORK SETTING

Settings of station address, baud rate, data allocation and 
cyclic expansion must be completed before mounting the 
module.

 

HOW TO MOUNT THE MODULE ON DIN RAIL

Hook

DIN Rail Adaptor

• Power/Network Module

Position the upper hook at the rear on the DIN rail and push in the lower.
When removing the module, push down the DIN rail adaptor utilizing a 
minus screwdriver and pull.

 

POWER/NETWORK MODULE

(CC-Link Ver.2.00; for 64-point analog signals)

MODEL

R8-NC3

INSTRUCTION MANUAL

Содержание R8-NC3

Страница 1: ...ox 12W output current 1 6 A Excitation supply 24V DC 10 operational current 10A ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing...

Страница 2: ...4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps front DIP SW Data Allocation Mode SW1 DATA ALLOCATION MODE SW1 1 ON 2 OFF Cyclic Expansion SW2 CYCLIC EXPANSION...

Страница 3: ...ON OFF OFF ON Unable to receive data addressed to the station ON ON OFF OFF OFF ON OFF BL BL ON Performs the interval timed responses but CRC error found in receiving the refresh data ON OFF BL BL OF...

Страница 4: ...nce bond the FE1 terminal to ground Caution FE1 terminal is NOT a protective conductor terminal EXC SUPPLY 24V INTERNAL POWER 5V PC CONFIGURATION JACK WIRING INSTRUCTIONS TENSION CLAMP TERMINAL BLOCK...

Страница 5: ...utput Data The figure below shows the allocation of data sent from the power network module to the master 0 Module 1 2 3 4 5 6 7 8 9 10 11 12 14 13 15 2 4 6 8 10 12 14 30 31 30 0 15 RWr n 0 Input Data...

Страница 6: ...H1 7_CH1 6_CH2 7_CH2 2 4 6 8 10 12 14 31_CH1 31_CH2 62 0 15 RWw n 0 16 m m cyclic expansion setting data areas are available for the R8 NC3 Field input data is set at the module s output data area The...

Страница 7: ...t binary data is used for temperature data With C K temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is di...

Отзывы: