R7ML-RS4

P. 5 / 10

EM-7805-C Rev.2

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque

: 0.5 N·m

 

SOLDERLESS TERMINAL  mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminal:
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

MECHATROLINK CONNECTION

 MECHATROLINK CONNECTION

SRD+
SRD–

SLD

Master

termi-

nator

termi-

nator

Terminator

  Be sure to connect the terminating resistors to the unit at both ends of transmission line.
  Use the terminating resistor dedicated for MECHATROLINK: Model JEPMC-W6022, Yaskawa Controls Co., Ltd.
 Certain types of Master units may have incorporated terminating resistors.  Consult the instruction manual for the Master.

SRD+
SRD–

SLD

SRD+
SRD–

SLD

Slave

SRD+
SRD–

SLD

SRD+
SRD–

SLD

Slave

SRD+
SRD–

SLD

MECHATROLINK

Cable

MECHATROLINK

Cable

*

*

MECHATROLINK COMMUNICATION

 

MECHATROLINK-I

Baud rate

: 4 Mbps

Transmission distance

: 50 m max.

Distance between stations

: 30 cm min.

Transmission media

: MECHATROLINK cable (Model JEPMC-W6003-x-E, Yaskawa Controls Co., Ltd.)

Max. number of slaves

:  15 (The maximum number of slaves might change depending on the master unit. Refer to the 

manual of the master unit)

Transmission cycle

: 2 msec. (fixed)

Data length

: 17 byte

 

MECHATROLINK-II

Baud rate

: 10 Mbps

Transmission distance

: 50 m max.

Distance between stations

: 50 cm min.

Transmission media

: MECHATROLINK cable (Model JEPMC-W6003-x-E, Yaskawa Controls Co., Ltd.)

Max. number of slaves

:  30 (The maximum number of slaves might change depending on the master unit. Refer to the 

manual of the master unit)

Transmission cycle

: 0.5 msec., 1 msec., 1.5 msec., 2 msec., 4 msec., 8 msec.

Data length

: 17 bytes / 32 bytes selectable (Must choose identical data size for all stations on one network)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7ML-RS4

Страница 1: ...rating 24V 10 approx 70mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are...

Страница 2: ...8 9 6 14 5 MECHATROLINK Setting Rotary SW MECHATROLINK Connector Station Address Setting Rotary SW Status Indicator LED Operating Mode Setting DIP SW SW1 PC Configurator Jack Power Supply Terminals M...

Страница 3: ...c ON 1 sec Burnout SW1 4 SW1 4 Burnout OFF Upscale ON Downscale RTD type SW1 5 1 6 1 7 1 8 SW1 5 SW1 6 SW1 7 SW1 8 RTD type OFF OFF OFF OFF Pt 100 JIS 97 IEC ON OFF OFF OFF Pt 100 JIS 89 OFF ON OFF OF...

Страница 4: ...2 95 CONNECTION DIAGRAM Connect the unit as in the diagram below EXTENSION CONNECTOR 10 INA0 2 INB0 11 INb0 INPUT 0 INA1 INB1 INb1 INPUT 1 INA2 INB2 INb2 INPUT 2 INA3 INB3 INb3 INPUT 3 12 4 13 15 7 1...

Страница 5: ...e SRD SRD SLD SRD SRD SLD Slave SRD SRD SLD MECHATROLINK Cable MECHATROLINK Cable MECHATROLINK COMMUNICATION MECHATROLINK I Baud rate 4 Mbps Transmission distance 50 m max Distance between stations 30...

Страница 6: ...0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK II in the 17 byte mode CD...

Страница 7: ...ESPONSE REMARKS 0 CDRW 03H ACK 01H Cyclic Data Read Write CDRW Command Link transmission Acknowledge ACK Positive response to CDRW 1 ID_RD 03H ID_RD 03H Read ID ID_RD Command Read out the device ID 2...

Страница 8: ...on cycle 8 0 0 9 0 0 10 0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK I...

Страница 9: ...id Command Command is not supported Warning 02H Command Not Allowed Command execution conditions are not met Warning 03H Invalid Data Data in the command is not correct Warning 04H Synchronization Err...

Страница 10: ...ugh 7 data are set R7ML EC16x R7ML EC8x Output data are repeated EXT IN HI Extension data high 8 bits R7ML EA16 Bit 8 through 15 data are set R7ML EC16x Output data are repeated R7ML EA8 R7ML EC8x Unu...

Отзывы: