R7M-DA16F

COMPONENT IDENTIFICATION

■ 

SIDE VIEW

■ 

FRONT VIEW

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

1 2 3 4 5 6 7 8

0 1 2 3 4 5 6 7

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED 
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  Discrete Input Status Indicator LED
(G)  Modbus, Power Supply Terminals
(H)  Input Terminals
( I )  Terminating Resistor SW

(A)

(G)

(H)

(B)

(C)

(D)

(E)

(F)

8 9 A B C D E F

CNFG.

(I)Terminating Resistor SW

TERM

ON

OFF

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 
normally.

RUN

Red

Turns on when the refresh data is received 
normally.

ERR

Red

Turns on when the received data is abnor-
mal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The 
left switch determines the tenths place digit, while the right 
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0: 38.4 kbps
1: 19.2 kbps
2: 9600 bps
3: 4800 bps
4: 2400 bps

5: 1200 bps
6: 14.4 kbps
7: 28.8 kbps
8: 57.6 kbps
9: 115.2 kbps

 

OPERATING MODE

• 

Extension (SW1-1, 1-2)

SW1-1

SW1-2 Extension

OFF

OFF

No extension (*)

ON

OFF

Discrete input 8 or 16 points

OFF

ON

Discrete output 8 or 16 points

(*) Factory setting
Note : Be sure to set unused SW1-3 through 1-8 to OFF.

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

6

7

1

2

3

DG +24V

0V

DB

SLD

FG

(1)  DB 

(2)  SLD 

Shield

(3)  FG 

FG

(4)  DA 

(5)  DG 

(6)  +24V 

Power input (24V DC)

(7)  0V 

Power input (0V)

 

INPUT TERMINAL ASSIGNMENT

10

COM

11

X1

12

X3

1

COM

2

X0

3

X2

13

X5

4

X4

14

X7

5

X6

15

X9

6

X8

16

XB

7

XA

17

XD

8

XC

9

XE

18

XF

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

COM

Common

10

COM

Common

2

X0

Input 0

11

X1

Input 1

3

X2

Input 2

12

X3

Input 3

4

X4

Input 4

13

X5

Input 5

5

X6

Input 6

14

X7

Input 7

6

X8

Input 8

15

X9

Input 9

7

XA

Input 10

16

XB

Input 11

8

XC

Input 12

17

XD

Input 13

9

XE

Input 14

18

XF

Input 15

 

EXTENSION MODULE

Combinations with all extension modules are available.

 

DISCRETE INPUT STATUS INDICATOR LED

LED indicators show the signal status.
  ON  : LED ON
  OFF : LED OFF

 

PC CONFIGURATOR

The following parameters can be set with using PC Configu-
rator Software.

• 

Modbus parameters: Parity, bit length, stop bit

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate. 
(Factory setting OFF)