background image

R7L-DC16B

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7804-H  Rev.7  P. 13 / 19

• Configuration Properties

CONFIGURATION
PROPERTY

NETWORK 
VARIABLE

TYPE
{ Range }
{ Default }

EXPLANATIONS

SCPTvalueDefinition[0...16]

----

{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}

Table (below) defines SCPTvalueDefinition[ ] 
value against each input status

• Input v.s. SCPTvalueDefinition

nviENIn1

nviENIn2

nviENIn3

nviENIn4

nvoENOut VALUE

OFF

OFF

OFF

OFF

SCPTvalueDefinition[0]

ON

OFF

OFF

OFF

SCPTvalueDefinition[1]

OFF

ON

OFF

OFF

SCPTvalueDefinition[2]

ON

ON

OFF

OFF

SCPTvalueDefinition[3]

OFF

OFF

ON

OFF

SCPTvalueDefinition[4]

ON

OFF

ON

OFF

SCPTvalueDefinition[5]

OFF

ON

ON

OFF

SCPTvalueDefinition[6]

ON

ON

ON

OFF

SCPTvalueDefinition[7]

OFF

OFF

OFF

ON

SCPTvalueDefinition[8]

ON

OFF

OFF

ON

SCPTvalueDefinition[9]

ON

ON

OFF

ON

SCPTvalueDefinition[10]

OFF

ON

OFF

ON

SCPTvalueDefinition[11]

ON

OFF

ON

ON

SCPTvalueDefinition[12]

OFF

OFF

ON

ON

SCPTvalueDefinition[13]

ON

ON

ON

ON

SCPTvalueDefinition[14]

OFF

ON

ON

ON

SCPTvalueDefinition[15]

Invalid in one or more nviENIn

SCPTvalueDefinition[16]

Содержание R7L-DC16B

Страница 1: ...ore you remove the unit or mount it turn off the power supply and output signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 5...

Страница 2: ...s stopped OFF Normal state DISCRETE OUTPUT STATUS INDICATOR LED Used to show discrete output signal status ON LED ON OFF LED OFF SERVICE SWITCH Used to identify the node in LONWORKS network configura tion RESET SWITCH Used to reset the Neuron Chip Press the switch behind the front cover to reset Control functions are halted while completing resetting and restarting Confirm no danger before conduct...

Страница 3: ...20 DIN RAIL 35mm wide 54 2 13 17 66 4 5 6 7 1 2 3 10 11 12 13 2 3 4 1 15 16 17 18 7 8 9 6 14 5 3 12 5 5 22 50 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for LONWORKS POWER 18 M3 SCREW TERMINALS for OUTPUT 6 24 6 24 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG NET2 NET2 NET1 NET1 Output Connection Example 10 17 18 1 YD 16 YB 0V YF 15 Y9 14 Y7 13 Y5 12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 24V Y0 2...

Страница 4: ...CONNECTION HOST PC LONWORKS R7L LONWORKS R7L LONWORKS Terminator WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 6 24 max 3 3 13 max mm inch ...

Страница 5: ...CPToemType SCPTserialNumber Extension module setting Maximum sending time per fb Minimum sending time per fb Set Tag No name Indicate Model No and Version Indicate Serial No NodeObject Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviRequest SNVT_obj_request For use with LonMaker and other tools nvoStatus SNVT_obj_status For use with ...

Страница 6: ...0 0 0 Maximum time interval to send network variables per fb Power supply must be reset when this configuration prop erty is changed Network variables are sent out in the specified intervals even when there is no change in the value No sending when a value less than 10 0 is set Invalid property when the assigned fb has no network vari ables to be sent to the network SCPTminSendTime Number of fb SN...

Страница 7: ...oCNTOut Set the maximum count Set the value when fbCNT is reset fbCNT SCPTdirection nviCNTIn SCPTinvrtOut nviCNTCtrl SCPTpwrUpState nvoCNTOut SCPTnvType SCPTmaxRnge SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCNTIn SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Counted object nviCNTCtrl SNVT_switch 0 0 0 100 0 1 Invalid 0 0...

Страница 8: ...p 1 Count always reset to 0 Bit 5 8 through 15 Invalid Minimum input pulse width 500 ms for nviCNTIn 50 ms for the input terminals DO NOT connect a network variable to nviCNTIn when one of the input terminals other than nviCNTIn is assigned as the counted object ON time per 1 second increments SCPTinvrtOut nviCNTIn SNVT_lev_disc ST_OFF ST_ON ST_OFF Count logic at nviCNTIn ST_OFF Count with nvoCNTI...

Страница 9: ... Y5 Y7 Y9 YB YD YF State Mode Output nviDO status Output nviDOOvr status Momentary Mode 1 or 2 One shot output at ON nviDO or nviDOOvr at ON One shot output at OFF nviDO or nviDOOvr at OFF nviDO SNVT_switch nviDOOvr SNVT_switch nv 68 nv 75 nv 60 nv 67 nv 76 nv 83 Output Terminal v s fbDO Network Variables nviDO nviDOOvr Assignments FUNCTIONAL BLOCK NETWORK VARIABLE OUTPUT TERMINAL fbDO 0 nviDO Y0 ...

Страница 10: ...nviDOOvr is other than Invalid One shot output is provided at either Y0 or Y1 depending upon nviDOOvr value nviDOOvr SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 nvoDOStat SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Outputs last one shot output status Configuration Properties Common CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0...

Страница 11: ...nviCMPIn2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Connects to the network variable to be compared nvoCMPOut SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 nviCMPIn1 and nviCMPIn2 are compared OFF is output when both val ues are equivalent ON or Invalid is output when they are not ON is output when nviCMPIn1 status change caused the discrepancy Invalid is output when nviCMPIn2 status change caused it OFF ...

Страница 12: ...viENIn1 SNVT_switch nv 112 nv 115 nviENIn2 SNVT_switch nv 116 nv 119 nviENIn3 SNVT_switch nv 120 nv 123 nviENIn4 SNVT_switch Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviENIn1 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Encoder input 1 nviENIn2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Encoder input 2 nviENIn3 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Encoder input 3 nviENIn4 SNVT...

Страница 13: ...In4 nvoENOut VALUE OFF OFF OFF OFF SCPTvalueDefinition 0 ON OFF OFF OFF SCPTvalueDefinition 1 OFF ON OFF OFF SCPTvalueDefinition 2 ON ON OFF OFF SCPTvalueDefinition 3 OFF OFF ON OFF SCPTvalueDefinition 4 ON OFF ON OFF SCPTvalueDefinition 5 OFF ON ON OFF SCPTvalueDefinition 6 ON ON ON OFF SCPTvalueDefinition 7 OFF OFF OFF ON SCPTvalueDefinition 8 ON OFF OFF ON SCPTvalueDefinition 9 ON ON OFF ON SCP...

Страница 14: ...r function With Invalid nvoTMROut is reset to the default status and the internal counter is reset nvoTMROut SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Timer output Configuration Properties Common CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 0 fbTMR operating mode 0 One shot mode 1 Cyclic mode Bit 1 through...

Страница 15: ...ains on Set Invalid at nviTMRIn to turn nvoTMROut off Example Providing one shot output when nviTMRIn is turned on SCPTtimeout 0 One shot output delay time SCPTtimeout 1 Pulse width SCPTtimeout 2 800 1 Holds nvoTMROut when nviTMRIn is turned off If SCPTtimeout 2 equals other than 800 1 the pulse width equals the addition of SCPTtimeout 1 and SCPTtimeout 2 Turning nvoTMROut on in a specific time pe...

Страница 16: ...ariables Configuration Properties Extension discrete output Y0 Y2 Y4 Y6 Y8 YA YC YE Output nviDOEX1 status Y1 Y3 Y5 Y7 Y9 YB YD YF Output nviDOEX2 status nv 4 nv 11 nviDOEX1 SNVT_switch nv 12 nv 19 nviDOEX2 SNVT_switch Output Terminal v s fbDOEX Network Variables nviDOEX1 nviDOEX2 Assignments FUNCTIONAL BLOCK NETWORK VARIABLE OUTPUT TERMINAL fbDOEX 0 nviDOEX1 Y0 nviDOEX2 Y1 fbDOEX 1 nviDOEX1 Y2 nv...

Страница 17: ... on or off Y1 Y3 Y5 Y7 Y9 YB YD YF of the extension module depending upon this input 100 0 1 ON Other OFF Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 1 Output held or not at power off 0 OFF at the power startup 1 Outputs the held status at the power startup Bit 0 Bit 2 through 1...

Страница 18: ... X8 XA XC XE X1 X3 X5 X7 X9 XB XD XF Normal Mode Status output at nvoDIEX1 Status output at nvoDIEX2 Combination Mode Refer to the table in the next page fbDIEX SCPTdirection nvoDIEX1 SCPTinvrtOut nvoDIEX2 SCPTinvrtOut Set operating mode Invert output Invert output Input Terminal v s fbDIEX Network Variables nvoDIEX1 nvoDIEX2 Assignments FUNCTIONAL BLOCK NETWORK VARIABLE INPUT TERMINAL fbDIEX 0 nv...

Страница 19: ...XC XE X1 X3 X5 X7 X9 XB XD XF nvoDIEX1 nvoDIEX2 OFF OFF 0 0 0 OFF Invalid ON OFF 100 0 1 ON Invalid OFF ON 0 0 0 OFF 0 0 0 OFF ON ON 100 0 1 ON 100 0 1 ON nvoDIEX2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 0 Bit 1 fbDIEX operating mode 0...

Отзывы: