R7HL-YS2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7812-E Rev.4 P. 3 / 5
■
NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT
• Full-duplex communication
4
RXD+
5
6
7
1
2
3
RXD– +24V 0V
TXD+ TXD– FG
NO.
ID
FUNCTION, NOTES
1
TXD+
Network (slave, transm)
2
TXD–
Network (slave, transmission –)
3
FG
FG
4
RXD+
Network (master, transm)
5
RXD–
Network (master, transmission –)
6
+24V
Power input (24V DC)
7
0V
Power input (0V)
• Half-duplex communication
4
TR
+
5
6
7
1
2
3
TR
– +
24V
0V
NC
NC
FG
NO.
ID
FUNCTION, NOTES
1
NC
No connection
2
NC
No connection
3
FG
FG
4
TR+
Network
5
TR–
Network
6
+24V
Power input (24V DC)
7
0V
Power input (0V)
■
OUTPUT TERMINAL ASSIGNMENT
6
NC
7
I0
8
NC
1
NC
2
COM0
3
NC
9
I1
4
COM1
10
NC
5
NC
NO.
ID
FUNCTION
NO.
ID
FUNCTION
1
NC
No connection
6
NC
No connection
2
COM0
Common 0
7
I0
Current 0
3
NC
No connection
8
NC
No connection
4
COM1
Common 1
9
I1
Current 1
5
NC
No connection
10
NC
No connection
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R7CON for detailed operation.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Zero scale
-32000 to +32000
0
Full scale
-32000 to +32000
10000
Bias
-320.00 to +320.00
0.00
Gain
-3.2000 to +3.2000
1.0000