WARNINGS AND CAUTIONS WHEN LAYING CABLES

Signal cables connected to the R7D contain high-frequency components.  Since these cables has the same effect as an an-
tenna, they emit these high-frequency components to the external space as noise or overlaps noise from the external space 
on themselves.
Cables with shielding should be used for the signal line due to the above reason.
EMC conformance test is conducted in the condition that shielded cables and earth clamps are used with the R7D.
Warning and cautions when laying cables are stated below.  These points of cautions are illustrated in the next page.

• Use shielded cables for those signal cables installed out of the control panel and for thermocouple and RTD extension wires.
• All the network cables connected to R7D should be shielded.
• Use exclusively designed network cables for the DeviceNet.
• Expose the shield at a part of the cable cover, clip it with an earth clamp, and ground it to the internal panel of the control 

panel.  A drain wire connected to the panel in a pig-tail form cannot maintain low impedance against high-frequency noise, 
thus grounding (noise shielding) in this form will not be effective.

Supplement: 

Additional measures may be taken depending upon actual installation sites.  These points of cautions are illustrated in the 
next page.

• Keep cables as short as possible.  It prevents noise emissions from the cables and noise overlapping to the cables.
• Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise.  Ferrite core can be attached close 

to the cable outlet of the control panel or close to the I/O terminal or connector, whichever is more effective.  Also, the impact 
might be reduced by winding the cable around the ferrite core for extra turns or attaching multiple ferrite cores.

• Keep cables which are easily affected by noise away from those which can be a noise source.

Motor Drive

Cable

Power Supply 

Cable

DC Signal Cable

Network Cable

Analog Signal

Cable

Often being a noise source

Often subject to noise interference.

In the following are examples of effective ways to lay cables separately: 

• Keeping physical distance (farther than 20 cm from motor drive cables, farther than 10 cm for other groups).
• Dividing off by a grounded metal plate
• Grouping into separate grounded metal pipes or cable shields.

Wires on each side of a filter should not be too close to each other.  Noise could ride onto the other side of cable.
Extra attention needs to be paid at the following parts.

• Noise filter that is enclosed in power cables.
• Ferrite core that is attached to signal cables.
• Noise limiting circuit (surge quenching circuit, transient absorber circuit, etc.) that is enclosed in signal cables.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7D-TS4/UL

Страница 1: ...t Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment mus...

Страница 2: ...artup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 through 9 it analyzes the PLC s network to determine the baud rate on the network OPERATING MODE Facto...

Страница 3: ...one byte characters within 8 characters CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING TC Type K CA E CRC J IC T CC B RH R S C WRe 5 26 N U L P Platinel II PR K CA Temp Unit C F K...

Страница 4: ...20 DIN RAIL 35mm wide 54 2 13 17 66 CONNECTION DIAGRAM 10 IN0 11 IN0 1 CJ0 2 CJ0 IN1 IN1 CJ1 CJ1 IN2 IN2 CJ2 CJ2 IN3 IN3 CJ3 CJ3 INPUT 0 12 13 3 4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 CAN_L V...

Страница 5: ...put Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Input Module without Status Example 2 Analog Input Module R7D EC16x with Status R7D EC16x Input D...

Страница 6: ...the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D ECx 0 1 STATUS Status signal can be included in the transmission data when the setting is ena...

Страница 7: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7D modul...

Страница 8: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 9: ...f cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impac...

Страница 10: ...applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it...

Отзывы: