R7D-TS4

EM-7802-B  Rev.10  P. 4 / 10

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

2 3 4

1

5

3 (.12)

3 (.12)

5.5 (.22)

50 (1.97)

18.5 (.73)

115 (4.53)

18–M3 SCREW 

TERMINALS

for INPUT

6 (.24)

TERMINAL BLOCK for

DeviceNet, POWER

7

(.28)

30 (1.18)

[5 (.20)]

DIN RAIL

35mm wide

54 (2.13)

17 (.66)

 

CONNECTION DIAGRAM

10

+IN0

11

–IN0

1

+CJ0

2

–CJ0

+IN1

–IN1

+CJ1

–CJ1

+IN2

–IN2

+CJ2

–CJ2

+IN3

–IN3

+CJ3

–CJ3

INPUT 0

12

13

3

4

INPUT 1

15

16

6

7

INPUT 2

17

18

8

9

INPUT 3

CAN_L

V–

Drain

CAN_H

V+

 Input Connection Example

+INn

–INn

+CJn

–CJn

T/C

+

CJC

SENSOR

+INn

–INn

Short

CJC

SENSOR

+CJn

–CJn

• 

Unused Input Channels

  Close across the unused input terminals as shown below.
   (Choose K (CA) thermocouple for unused channels.)

EXTENSION CONNECTOR

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7D-TS4/UL

Страница 1: ...t Altitude up to 2000 meters This equipment must be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment mus...

Страница 2: ...artup with the switch set to the positions 0 125 kbps 1 250 kbps or 2 500 kbps For the settings 3 through 9 it analyzes the PLC s network to determine the baud rate on the network OPERATING MODE Facto...

Страница 3: ...one byte characters within 8 characters CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING TC Type K CA E CRC J IC T CC B RH R S C WRe 5 26 N U L P Platinel II PR K CA Temp Unit C F K...

Страница 4: ...20 DIN RAIL 35mm wide 54 2 13 17 66 CONNECTION DIAGRAM 10 IN0 11 IN0 1 CJ0 2 CJ0 IN1 IN1 CJ1 CJ1 IN2 IN2 CJ2 CJ2 IN3 IN3 CJ3 CJ3 INPUT 0 12 13 3 4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 CAN_L V...

Страница 5: ...put Module Status CH0 CH1 CH2 Begin 0 Begin 0 1 2 CH3 3 4 Output Data Input Data None Example 1 Analog Input Module without Status Example 2 Analog Input Module R7D EC16x with Status R7D EC16x Input D...

Страница 6: ...the extension module is added MODEL OUTPUT DATA 1 INPUT DATA 2 R7D to Master Master to R7D R7D EAx 1 0 R7D ECx 0 1 STATUS Status signal can be included in the transmission data when the setting is ena...

Страница 7: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7D modul...

Страница 8: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 9: ...f cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impac...

Страница 10: ...applicable when wiring the R7D Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it...

Отзывы: