R7C-YS2

EM-7801-E  Rev.5  P. 8 / 10

Use (e.g.) a shield cover 
when noise leaks through 
the opening.

To external apparatus

Keep the opening

for cabling as small as

possible.

Install an electromagnetically
shielded gasket when 
noise leaks through 
the opening.

Shielding is strengthened 
by using an electro-
magnetically shielded 
control panel.

By connecting the
internal panel plate 
and the panel cover with 
an earth strap, grounding 
may be strengthened and
EMC may be improved.

Ground the control panel 

at low impedance using 

 (e.g.) braided wires.

Keep the opening for 

ventilation as small as

posible.

Attach an electro-
magnetically shielded
filter when noise leaks 
through the opening.

Install the R7C Series inside

a control panel.

Attachment part of earth

clamp should be fixed with 

screw in conduction with the

internal panel plate.

• Points of cautions applicable when installing the R7C Series

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7C-YS2

Страница 1: ...ion environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the C...

Страница 2: ...Station Address Setting x1 Station Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps...

Страница 3: ...the station due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Stati...

Страница 4: ...POWER 10 M3 SCREW TERMINALS for OUTPUT DIN RAIL 35mm wide 54 2 13 17 66 6 24 50 1 97 6 24 18 5 73 115 4 53 CONNECTION DIAGRAM 4 7 6 3 2 5 1 0V 24V DC FG SLD DG DB DA 7 I0 2 COM0 9 4 OUTPUT 0 I1 COM1 O...

Страница 5: ...munication line DATA ALLOCATION Unused Unused Unused Unused RWrn 0 1 2 3 Analog output 0 Analog output 1 Unused Unused RWwn 0 1 2 3 Interval timed Response X Refresh Data Y Unused Reserved Unused Rese...

Страница 6: ...ut 7 Output 7 Input 8 Output 8 0 OFF 1 ON DISCRETE I O WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade...

Страница 7: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module...

Страница 8: ...d the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 9: ...ions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to t...

Страница 10: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To con...

Отзывы: