R7C-DC8E

P.  / 5

EM-780-AG

 

STATUS INDICATOR LED

  ID 

COLOR  FUNCTION

 

 PWR 

Red 

Turns on when the internal 5V is sup-

plied normally.

 RUN 

Red 

Turns on when the refresh data is re-

ceived normally.

  ERR 

Red 

Turns on when the received data is 

abnormal.

  SD 

Red 

Turns on when the module is transmit-

ting.

  RD 

Red 

Turns on when the module is receiving.

 STATION ADDRESS

Station Address  is  selected  between  1  and  64  in  decimal.  
The left switch determines the tenth place digit, while the 
right switch does the ones place digit of the address.

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

Station Address Setting (x1)

Station Address Setting (x10)

5

4

3

2 1 0 9

8

7

6

Baud Rate Setting

0 : 156 kbps

1 : 625 kbps

2 : 2.5 Mbps

3 : 5 Mbps

4 : 10 Mbps

• Output at the loss of communication (SW1-5)

 SW1-5  Output at the loss of communication

 

  OFF  Reset the output (turned off)
  ON 

Hold the output (*) 

 

 

 

(maintains the last data received normally)

(*) Factory setting
Caution ! - SW 1-6 through 1-8 are unused.  Be sure to 

turn off unused ones.

10

+24V

11

Y0

12

Y1

1

0V

2

COM0

3

COM0

13

Y2

4

COM0

14

Y3

5

COM0

15

Y4

6

COM1

16

Y5

7

COM1

17

Y6

8

COM1

9

COM1

18

Y7

 

 

NO. 

ID 

FUNCTION 

NO.  ID 

FUNCTION

  1 

0V 

0V 

10  +24V  24V DC

  2  COM0  Common 0 

11  Y0 

Output 0

  3  COM0  Common 0 

12  Y1 

Output 1

  4  COM0  Common 0 

13  Y2 

Output 2

  5  COM0  Common 0 

14  Y3 

Output 3

  6  COM1  Common 1 

15  Y4 

Output 4

  7  COM1  Common 1 

16  Y5 

Output 5

  8  COM1  Common 1 

17  Y6 

Output 6

  9  COM1  Common 1 

18  Y7 

Output 7

 POWER SUPPLY, CC-LINK TERMINAL ASSIGNMENT

4

DA

5

DG

6

+24V

1

DB

2

SLD

3

FG

7

0V

 

 

NO. 

ID 

FUNCTION, NOTES

  1 

DB 

White

  2 

SLD 

Shield

  3 

FG 

FG

  4 

DA 

Blue

  5 

DG 

Yellow

  6 

+24V 

Power input (24V DC)

  7 

0V 

Power input (0V)

 OUTPUT TERMINAL ASSIGNMENT

 BAUD RATE

Baud Rate is selected with the rotary switch.

COMPONENT IDENTIFICATION

TERM

ON

OFF

(H)

� 

SIDE VIEW

� 

FRONT VIEW

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

STATION ADD.

B.RATE

1 2 3 4 5 6 7 8

0 1 2 3 4 5 6 7

4

5

6

7

1

2

3

10 11

12 13

2

3

4

1

15 16

17 18

7

8

9

6

14

5

(A)  Status Indicator LED 

*

1

(B)  Station Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  Discrete I/O Status Indicator LED
(F)  CC-Link, Power Supply Terminals
(G)  Output Terminals
(H)  Terminating Resistor SW

*

1. Refer to ʻStatus Indicator LEDʼ section for detailed information.

(A)

(F)

(G)

(B)

(C)

(D)

(E)

• Extension (SW1-1, 1-2, 1-3, 1-4)

 

SW1-1  SW1-2  SW1-3  SW1-4  Extension

 

  OFF 

ON 

OFF 

OFF  No extension (*)

  OFF 

ON 

OFF 

ON 

Discrete output, 16 points

 OPERATING MODE

 TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate.  (Factory setting OFF)