R7C-DC8E

P.  / 5

EM-780-AG

 

STATUS INDICATOR LED

PWR  RUN  ERR 

SD 

RD 

STATUS

 ON 

ON 

FL 

FL 

ON  Communicates normally with occasional CRC errors due to noise interference.

 ON 

ON 

FL 

FL 

ON  Communicates normally but the Baud Rate and/or Station Address switches failed.  

ERR LED flashes approximately in 0.5 second intervals.

 ON 

ON 

FL 

FL 

OFF  ----

 ON 

ON 

FL 

OFF  ON  CRC error found in the received data.  Unable to respond.

 ON 

ON 

FL 

OFF  OFF  ----

 ON 

ON  OFF 

FL 

ON  Normal communication

 ON 

ON  OFF 

FL 

OFF  ----

 ON 

ON  OFF  OFF  ON  Unable to receive data addressed to the station.

 ON 

ON  OFF  OFF  OFF  ----

 ON  OFF 

FL 

FL 

ON  Performs the interval-timed responses but CRC error found in receiving the refresh 

data.

 ON  OFF 

FL 

FL 

OFF  ----

 ON  OFF 

FL 

OFF  ON  CRC error found in the data addressed to the station.

 ON  OFF 

FL 

OFF  OFF  ----

 ON  OFF  OFF 

FL 

ON  Link is not started.

 ON  OFF  OFF 

FL 

OFF  ----

 ON  OFF  OFF  OFF  ON  No data addressed to the station.  Or unable to receive data addressed to the station 

due to noise interference.  (Missing parts of the data sent from the master)

 ON  OFF  OFF  OFF  OFF  Unable to receive data due to wire breakdown
 ON  OFF  ON  OFF  ON/OFF  Faulty Baud Rate and/or Station Address setting
 OFF  OFF  OFF  OFF  OFF  Power input removed.  Or power supply failure.

OFF = OFF, ON = ON, FL = Flashing

---- = Inconceivable in normal operations (e.g. LED failure)

 DISCRETE I/O STATUS INDICATOR LED

Discrete I/O modules including those for extensions have LED indicators showing I/O signal status.
     

Contact ON  : LED ON

     

Contact OFF  : LED OFF