POWER SUPPLY MODULE

MODEL

R5-PS1

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

n

 PACKAGE INCLUDES:

  Power supply module .................................................. (1)

n

 MODEL NO.

Confirm that the Model No. marking on the product is exactly 
what you ordered.

n

 INSTRUCTION MANUAL

This manual describes necessary points of caution when you 
use this product, including installation, connection and basic 
maintenance procedures.

POINTS OF CAUTION

n

 CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for use in Installation Category 

II (power input), Measurement Category II (RUN contact 
output) and Polution Degree 2.  Reinforced insulation (in-
ternal power or RUN contact output to power input to FG: 
300V) and basic insulation (internal power to RUN contact 
output: 300V) are maintained.  Prior to installation, check 
that the insulation class of this unit satisfies the system 
requirements.

• The equipment must be mounted inside a panel.
• Insert a noise filter for the power source connected to the 

unit.  Densei-Lambda Noise Filter Model MZS-1206-33 or 
equivalent is recommended.

• The actual installation environments such as panel con

-

figurations, connected devices and connected wires may 
affect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

n

 POWER INPUT RATING & OPERATIONAL RANGE

• Check the power rating for the unit on the specification label.

 

AC power

: 85 – 132V or 170 – 264V, 47 – 66 Hz, 

     

approx. 90VA

 

DC power

: 24V ±10%, approx. 45W, approx. 1.8A

n

 UNPLUGGING THE UNIT

• Before you remove the unit from its base or mount it, turn 

off the power supply for safety.

n

 ENVIRONMENT

• Indoor use
• When  heavy  dust  or  metal  particles  are  present  in  the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 

in order to ensure adequate life span and operation.

n

 WIRING

• Do not install cables close to noise sources (relay drive cable, 

high frequency line, etc.).

• Do not bind these cables together with those in which noises 

are present.  Do not install them in the same duct.

n

 RUN CONTACT OUTPUT

• Function of RUN contact output

  During a Network Module communicates normally with 

a master device (PLD or PC etc.), RUN contact output of 
Power Supply Module turns ON. 

• When using with dual redundant communication or two 

system.

  During both Network Module or one of them communicates 

normally with a master device (PLD or PC etc.), RUN contact 
output of Power Supply Module turns ON.

• When using R5-PS with redundant or two system.

  RUN contact output works in same function for both cases.  

However, when I/O capacity code of installation base is 
"05:5 slots (single network module)" or "09: 9 slots (single 
network module)", the RUN contact output of Power Supply 
Module installed in a Extender Power Module Base (model: 
R5-EX1) is not available.

n

 AND ....

• The unit is designed to function as soon as power is supplied, 

however, a warm up for 10 minutes is required for satisfying 
complete performance described in the data sheet.

INSTALLATION

Use the Installation Base (model: R5-BSx) or the Extender 
Power Module Base (model: R5-EX1).
In order to separate the Power Supply Module from a base, 
push the recess at the center of the locking clamp (See below) 
with a minus screwdriver.

Recess