manualshive.com logo in svg
background image

R30NCIE1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9020  Rev.3  P. 6 / 13

0

  0

RX(n+0)

Remote READY

Module Status (R30 Series)

Module Status (R3 Series)

Error Status (R30 Series)

Data Error Status (R30 Series)

Error Status (R3 Series)

Data Error Status (R3 Series)

15

  2   1

  A

  B

  C

  D

  E

  3

  F

  9   8   7   6   5   4

RX(n+3)

RX(n+4)

RX(n+5)

RX(n+6)

RX(n+2)

RX(n+1)

RX(n+7)

Unused

• RX(n+0)0 to 7 is reservation area, RX(n+0) is used as Ready signal, the bit is “1” when this module is in normal.

  RX(n+0)8 to A, RX(n+0)C to F are not used.

• Module Status

  RX(n+1)0 to RX(n+1)F indicate whether individual I/O modules of R30 series are mounted or not .
  RX(n+2)0 to RX(n+2)F indicate whether individual I/O modules of R3 series are mounted or not.
  The bit corresponding to the mounted slot turns to “1”, and the unmounted slot to “0”.

• Error Status 

  RX(n+3)0 to RX(n+3)F indicate error status for each module of R30 series.
  The bit corresponding to such module turns to “1”, as described below.
    R30X16(under development) input power in error or disconnected.
    R30Y16(under development) output current in error (e.g. load unconnected)
    RX(n+4)0 to RX(n+4)F indicate error status for each module of R3 series.
  The bit corresponding to such module turns to “1”, as described below.
    R3-TSx, R3-RSx, R3-US4 input burnout
    R3-DA16A input power in error or disconnected
    R3-YSx output current error (e.g load unconnected)
    R3-PC16A external power supply in error or disconnected

• Data Error Status

  RX(n+5)0 to RX(n+5)F indicate data error status for each module of R30 series.
  The bit corresponding to such module turns to “1”, as described below.
    Input value is out of -15% to 115%
    R30TS4, R30RS4, R30USx input burnout
  RX(n+6)0 to RX(n+6)F indicate error status for each module of R3 series.
  The bit corresponding to such module turns to “1”, as described below.
    Input value is out of -15% to 115%
    In the case of R3-US4 (voltage input) input level out of -10% to 110%.

     

RX(n+1)0, RX(n+3)0, RX(n+5)0 

R30 series slot 1

     

RX(n+1)1, RX(n+3)1, RX(n+5)1 

R30 series slot 2

     

RX(n+1)2, RX(n+3)2, RX(n+5)2 

R30 series slot 3

 

 

    

:

     

RX(n+1)F, RX(n+3)F RX(n+5)F 

R30 series slot 16

     

RX(n+2)0, RX(n+4)0, RX(n+6)0 

R3 series extension slot 1 

     

RX(n+2)1, RX(n+4)1, RX(n+6)1 

R3 series extension slot 2 

     

RX(n+2)2, RX(n+4)2, RX(n+6)2 

R3 series extension slot 3

 

 

    

:

     

RX(n+2)F, RX(n+4)F, RX(n+6)F 

R3 series extension slot 16

Link devices other than the above are not in use.

Содержание R30NCIE1

Страница 1: ...o ensure the CE conform ity HOT SWAPPABLE MODULES It is possible to replace a module with the power supplied provided that the module is replaced with one with the same model number and installed in t...

Страница 2: ...lic Transmitting ON In action OFF Not complied with ERR Red Error ON Abnormality node OFF Normal CN1 LINK Green CN1 Linking Up ON Linking up OFF Link down L ER Red CN1 Receiving Data ON Abnormality re...

Страница 3: ...age the positioning guide of the module with the In stallation Base 2 Pivot the module on the positioning guide and press it down until the lock tab clicks into place Positioning Guide 3 Tighten the b...

Страница 4: ...e unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 110 4 33 25 98 98 3 86 CONNECTION DIAGRAM CC Link IE Field CN1 CC Link IE Field CN2 Regarding CN1 and CN2 of RJ 45 connector for CC Link...

Страница 5: ...4 5 R30XN16A 1 6 R30XN16A 1 7 R30YN16A 1 8 R30YN16A 1 R30EBS04 1 R3 SV8 8 2 R3 YV8 8 3 R3 DA32A 2 4 R3 DC32A 2 0 15 RWr n 0 Slot 1 2 4 6 8 10 12 14 Slot 2 Slot 3 Slot 4 INPUT DATA The figure below sho...

Страница 6: ...nt output current in error e g load unconnected RX n 4 0 to RX n 4 F indicate error status for each module of R3 series The bit corresponding to such module turns to 1 as described below R3 TSx R3 RSx...

Страница 7: ...els R30SV4 R30SV2 R30YV4 R30YS4 R30US4 etc 16 bit binary data Basically 0 to 100 of the selected I O range is converted into 0 to 10000 binary Negative percentage is represented in 2 s complements 0 1...

Страница 8: ...energy Lower 16 bits are allocated from the lowest address to higher ones higher 16 bits in turn 0 15 0 Lower 16 bits 0 15 1 Higher 16 bits ANALOG DATA 32 bit data models R3 BA32A BC32A etc 32 bit bin...

Страница 9: ...after referred to as GX Works2 REGISTRATION FOR PROFILE This unit supports CC Link Family system profile CSP CSP can be downloaded from the CC Link Partner Association s home page http www cc link org...

Страница 10: ...ice station are connected by Ethernet cable CN1 and CN2 of CC Link IE Field Network RJ 45 modular jacks can be connected in any order Before wiring make sure to turn off the power of each unit 2 After...

Страница 11: ...work No 1 1 Check 2 Input 3 Click 4 Click 5 Click CC IE Field Configuration Setting to open the window of configuration setting In accordance with the actual system configuration select the model from...

Страница 12: ...EM 9020 Rev 3 P 12 13 6 Click Refresh Parameter to open the Refresh Parameter Setting window Assign link devices RX RY RWw RWr to CPU unit then click End 2 Click 1 Paste 7 Click End on the MELSECNET C...

Страница 13: ...is possible to check error point cause of error and event history and to monitor other stations 1 From the main menu select Diagnostics CC IE Field Diagnostics to display the CC IE Field Diagnostics w...

Отзывы: