COMPONENT IDENTIFICATION
CN1
CN2
×10
×1
STATION No.
CONFIG
L ER
LINK
L ER
LINK
RUN
RD
SD
D LINK
ERR
NCIE1
■
FRONT VIEW
■
BOTTOM VIEW
■
SIDE VIEW
Status Indicator LEDs
PC Configurator Connector
CC-Link IE Field Communication
RJ-45 Modular Jack
Station No. Rotary SW
Lock Tab
Base Fixing Screw
Positioning Guide
Specifications
■
STATUS INDICATOR LED
ITEM
ID
COLOR
FUNCTION
STATUS
DESCRIPTION
Status
Indicator
RUN
Green
Device State
ON
Normal
OFF
Indication of abnormality node
RD
Green
Receiving Data
ON
Receiving
OFF
SD
Green
Sending Data
ON
Sending
OFF
Unsent
D LINK
Green
Cyclic Transmitting
ON
In action
OFF
Not complied with
ERR
Red
Error
ON
Abnormality node
OFF
Normal
CN1
LINK
Green
CN1 Linking Up
ON
Linking up
OFF
Link-down
L ER
Red
CN1 Receiving Data
ON
Abnormality receiving data
OFF
Normality receiving data
CN2
LINK
Green
CN2 Linking Up
ON
Linking up
OFF
Link-down
L ER
Red
CN2 Receiving Data
ON
Abnormality receiving data
OFF
Normal
■
STATION NO. SETTING ROTARY SW
The upper rotary SW sets the upper digits (MSB), and the lower rotary SW sets the lowest digit (LSB) (configurable range is
1 to 120).
Confirm available station numbers in the manual of the master unit (Factory setting: 01H).
3
For setting MSB of Station No. (×10)
For setting LSB of Station No. (×1)
8
67
34 5
2
1
0
F E D C B A
9
5
4
2
1
0
9
8
7
6
Example of Station No. setting
Characters on Rotary SW for MSB represent; A: 10, B: 11, C: 12.
For example, to set station No. 115, set the SW for MSB to B and SW for LSB to 5.
Do NOT set to D, E, F as they are not in use.