R3-PD16C
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8425 Rev.2 P. 2 / 9
COMPONENT IDENTIFICATION
1
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
7
8
9
10
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
FRONT VIEW
SIDE VIEW
RUN LED
ERR LED
Status Indicator
LED
SW3
ON
4
3
2
1
Functions
Data Length
Output Mode
Output Hold
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
SW1
Output
ON Time
ON/OFF Control
Output Channel
Functions
ON
SW2
ON
I/O Mode
■
■
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/ green) LED;
Green in normal operating conditions;
Red with abnormal configuration.
Output status indicator
: Red LED; turns on with the output
ON.
■
SIDE DIP SW
(*)Factory setting
• I/O Mode Setting: SW2-7
Set output operation mode (Whether Output Complete Sta-
tus indicator is ON or OFF) *
1
SW
I/O MODE
Input and Output
Output
SW2-7
OFF (*)
ON
*1. Output completion status is compatible with interface
modules model: R3-NC1, -NC3, -NE1, -NM1 and -NDx of
firmware version V2.00 or higher. Other interface modules
are not compatible. So, set I/O Mode as output (SW2-7:
ON) to use it.
Note 1: R3-NL1 and R3-NL2 are not available with this model.
• ON/OFF Control Output Channel: SW2-8
ON/OFF control output channel is swappable with its pair.
SW
ON/OFF CONTROL OUTPUT CHANNEL
Not Swapped
Swapped
SW2-8
OFF (*)
ON
• Output Hold Function: SW3-1
Effective only in continuance output mode
SW
OUTPUT HOLD FUNCTION
HOLD
OFF
SW3-1
OFF (*)
ON
• Output Mode: SW3-2, 3-3
SW
OUTPUT MODE
SW3-2
SW3-3
OFF
OFF
One-Shot Output Mode (*)
ON
OFF
ON/OFF Control Output Mode
OFF
ON
Continuance Output Mode
• Output Data Length: SW3-4
Effective only in ON/OFF control output mode
SW
OUTPUT DATA LENGTH
16 bit
8 bit
SW3-4
OFF (*)
ON
• Output ON time: SW1
For setting Output ON time, DIP switch 1 through 8 correspond to each binary digit 1st through 8th digit. For every setting,
ON time will be as indicated below.
SW
OUTPUT ON TIME (sec.)
0.1 (
*
)
0.2
0.3
0.4
0.5
...
25.5
25.6
SW1-1
OFF
ON
OFF
ON
OFF
...
OFF
ON
SW1-2
OFF
OFF
ON
ON
OFF
ON
ON
SW1-3
OFF
OFF
OFF
OFF
ON
ON
ON
SW1-4
OFF
OFF
OFF
OFF
OFF
ON
ON
SW1-5
OFF
OFF
OFF
OFF
OFF
ON
ON
SW1-6
OFF
OFF
OFF
OFF
OFF
ON
ON
SW1-7
OFF
OFF
OFF
OFF
OFF
ON
ON
SW1-8
OFF
OFF
OFF
OFF
OFF
ON
ON