background image

R3-PD16C

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8425  Rev.2  P. 8 / 9

DATA ASSIGNMENT

 

Do

0

15

Do 1
Do 2
Do 3

Do 16

Note: For 8-bit length ON/OFF control mode, Do 9 through Do 16 are unavailable.

 

Di

0

15

Di 1
Di 2
Di 3

Di 16

Note: Di data is not practical discrete input data.  It is “output completion status” internal data.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

1

11
12
13
14
15
16
17
18
19
20

2
3
4
5
6
7
8
9

10

130 (5.12)

27.5 (1.08)

109 (4.29)

POSITIONING

GUIDE

TERMINAL

COVER

20–M3

SCREW

6.2

(.24)

Содержание R3-PD16C

Страница 1: ...er hot swapping modules Data is synchronized with data stored in the interface module in the initial commu nication after hot swapping Data will not be output from a channel even if 1 is previ ously written in Do before hot swapping or the PLC PC writes 1 to Do when communication has started after hot swapping Be sure to write 0 then 1 to Do in the initial communication When R3 PD16C is used in co...

Страница 2: ...odel R3 NC1 NC3 NE1 NM1 and NDx of firmware version V2 00 or higher Other interface modules are not compatible So set I O Mode as output SW2 7 ON to use it Note 1 R3 NL1 and R3 NL2 are not available with this model ON OFF Control Output Channel SW2 8 ON OFF control output channel is swappable with its pair SW ON OFF CONTROL OUTPUT CHANNEL Not Swapped Swapped SW2 8 OFF ON Output Hold Function SW3 1...

Страница 3: ...3 Ch1 One Shot Output Completion 4 5 7 8 9 2 One Shot Output ON OFF CONTROL OUTPUT MODE Data Length 16 bits Example that ON OFF control outputs sequentially Ch1 to Ch2 to Ch2 is shown below Example of when I O Mode is in Output Operation SW2 7 OFF and ON OFF Control channel is Not Swapped SW2 8 OFF 1 Output data Do 1 changes from 0 to 1 2 After Do 1 s rising edge Ch1 s one shot output turns ON for...

Страница 4: ...pletion Di 2 Ch2 output completed status changes from 0 to 1 4 When Do 1 changes from 1 to 0 Di 2 changes from 1 to 0 5 After Do 1 s sinking edge Ch1 s one shot output turns ON for a fixed period of time SW1 s time set 6 After one shot output completion Di 1 Ch1 output completed status changes from 0 to 1 Do 1 Ch2 Ch1 1 4 3 Ch2 One Shot Output Completion 6 Ch1 One Shot Output Completion Note Durin...

Страница 5: ...mpletion Status 0 Ch5 Output Completion Reset Do 6 1 Ch6 Output Di 6 Ch6 Output Completion Status 0 Ch6 Output Completion Reset Do 7 1 Ch7 Output Di 7 Ch7 Output Completion Status 0 Ch7 Output Completion Reset Do 8 1 Ch8 Output Di 8 Ch8 Output Completion Status 0 Ch8 Output Completion Reset Do 9 1 Ch9 Output Di 9 Ch9 Output Completion Status 0 Ch9 Output Completion Reset Do 10 1 Ch10 Output Di 10 ...

Страница 6: ...Output Completion Status 0 1 Ch8 Output Di 8 Ch8 Output Completion Status 1 1 Output Data Reset Do 9 Do 10 0 0 Not Operating 1 0 Ch9 Output Di 9 Ch9 Output Completion Status 0 1 Ch10 Output Di 10 Ch10 Output Completion Status 1 1 Output Data Reset Do 11 Do 12 0 0 Not Operating 1 0 Ch11 Output Di 11 Ch11 Output Completion Status 0 1 Ch12 Output Di 12 Ch12 Output Completion Status 1 1 Output Data Re...

Страница 7: ...he case of Not Swapped SW2 8 OFF ON OFF control output is swapped with its pair when SW2 8 is ON The following is an example of Do 1 Do WRITE ONE SHOT OUTPUT RESET Di OUTPUT COMPLETION STATUS Do 1 0 Ch2 Output Di 2 Ch2 Output Completion Status 1 Ch1 Output Di 1 Ch1 Output Completion Status CONTINUANCE OUTPUT MODE Do 1 through 16 are assigned to and Ch1 through 16 When data Do is 1 output is ON and...

Страница 8: ... length ON OFF control mode Do 9 through Do 16 are unavailable Di 0 15 Di 1 Di 2 Di 3 Di 16 Note Di data is not practical discrete input data It is output completion status internal data TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 1 11 12 13 14 15 16 17 18 19 20 2 3 4 5 6 7 8 9 10 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE TERMINAL COVER 20 M3 ...

Страница 9: ...ing tongue terminal size Spade tongue type is also applicable Solder less terminals with insulation sleeve do not fit Applicable wire size 0 3 0 5 mm2 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 12max 6max 3max 4min 3 2 dia mm FUNCTIONS OUTPUT HOLD or OUTPUT OFF In normal conditions the module outputs the signal from the preferred bus A When an error is detected th...

Отзывы: