R3-PD16A
P. 5 / 10
EM-8397 Rev.1
•
Data Length:
8 bits
Example that ON/OFF control outputs sequentially Ch2 to Ch1 is shown below.
Example of when I/O Mode is in Output Operation (SW2-7: OFF) and ON/OFF Control channel is Not Swapped (SW2-8:
OFF).
(1) Output data Do 1 changes from 0 to 1.
(2) After Do 1’s rising edge, Ch2’s one-shot output turns ON for a fixed period of time (SW1’s time set).
(3) After one-shot output completion, Di 2 (Ch2 output completed status) changes from 0 to 1.
(4) When Do 1 changes from 1 to 0, Di 2 changes from 1 to 0.
(5) After Do 1’s sinking edge, Ch1’s one-shot output turns ON for a fixed period of time (SW1’s time set).
(6) After one-shot output completion, Di 1 (Ch1 output completed status) changes from 0 to 1.
■
CONTINUOUS OUTPUT MODE
Example of Ch1 is shown below.
Example of I/O Mode is in Output Operation. (SW2-7: OFF)
Do 1
Ch2
Ch1
Note. During one shot output is on, rising edge and sinking edge are not detected.
(1)
(4)
(3) Ch2 One Shot Output Completion
(6) Ch1 One Shot Output Completion
Note. During one shot output is on, rising edge and sinking edge are not detected.
(5) One Shot Output
(2) One Shot Output
Di 1
(Ch1 Output Completion Status)
Di 2
(Ch2 Output Completion Status)
Do 1
Ch1
Di 1
(Ch1 Output Completion Status)