R3-NF2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8438 Rev.1 P. 3 / 5
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
130 (5.12)
27.5 (1.08)
109 (4.29)
10 (.39)
1
2
3
4
5
6
TERMINAL
COVER
6–M3
SCREW
6.2
(.24)
POSITIONING
GUIDE
■
CONNECTION DIAGRAM
INTERNAL POWER
INTERNAL
BUS
CONFIGURATION JACK
JACK
BUS CONNECTOR
*
When the module is at an end of the transmission line via
twisted-pair cable (= when there is no cross wiring), close
across the RT+ and RT– terminals with the jumper included
in the product package. Remove the jumper for all other locations.
**
Not provided with ‘No Power Supply’ type module.
Caution: FG terminal is NOT a protective conductor terminal.
1
4
RUN
+
RUN
–
RUN CONTACT OUTPUT
2
3
6
U (+)
V (–)
FG
POWER INPUT
**
**
RT+
RT–
SD
T2
T1
To Other
T-Link
Devices
–
+
Shielded Twisted-pair
Cable
Close to terminate
*
WIRING INSTRUCTIONS
■
M3 SCREW TERMINAL (power input, RUN contact output)
Torque: 0.5 N·m
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.75 to 1.25 mm
2
12max
6max
3max
4min
3.2 dia.
(mm)
■
EURO TYPE CONNECTOR TERMINAL (T-Link)
Applicable wire size: 0.2 to 2.5 mm
2
(AWG24 to 12)
Stripped length: 7 mm