COMPONENT IDENTIFICATION

RUN LED

ERR LED

SW3

SA1

SA2

ON

4

3

2

1

1

2

3

4

5

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Configuration Jack

Node Address Setting

Rotary SW (MSB)

Node Address Setting

Rotary SW (LSB)

n SIDE VIEW

n FRONT VIEW

Functions

RT+

RT–

SD

T2

T1

Euro Type
Connector Terminal

 

FRONT ROTARY SW

• Node Address: SA1, SA2

Node Address is set in decimal.
(Setpoint adjustment: 00 – 99)

 

SIDE DIP SW

(*) Factory setting 

• Dual Communication: SW3-1

When two network modules are mounted, one must be 
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work.  For single communication, the network module must 
always be set to ‘Main’ (OFF).

SW

DUAL COMMUNICATION

MAIN

SUB

SW3-1

OFF (*)

ON

• Input Error Data: SW3-2

Hold: When the communication from an input module is lost 
due to the input module error, the network module holds the 
signal and stands by until the communication recovers.
Set to ‘0’: When the communication from an input module 
is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD

SET ‘0’

SW3-2

OFF (*)

ON

• LED Function: SW3-4

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED FUNCTION

RUN

ERR

OFF(*)

Green when normal

Green ON or blink-
ing when abnormal

ON

Red blinking when 
receiving

Red blinking when 
transmitting

Note: Be sure to set unused SW3-3 to OFF.

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.

 

NETWORK MODULE SETTING 

PARAMETER

AVAILABLE RANGE

DEFAULT SETTING

Time (no communication time)

0.2 – 3200.0 (sec.)

3.0 (sec.) 