COMPONENT IDENTIFICATION
RUN LED
ERR LED
SW3
SA1
SA2
ON
4
3
2
1
1
2
3
4
5
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Configuration Jack
Node Address Setting
Rotary SW (MSB)
Node Address Setting
Rotary SW (LSB)
n SIDE VIEW
n FRONT VIEW
Functions
RT+
RT–
SD
T2
T1
Euro Type
Connector Terminal
■
FRONT ROTARY SW
• Node Address: SA1, SA2
Node Address is set in decimal.
(Setpoint adjustment: 00 – 99)
■
SIDE DIP SW
(*) Factory setting
• Dual Communication: SW3-1
When two network modules are mounted, one must be
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work. For single communication, the network module must
always be set to ‘Main’ (OFF).
SW
DUAL COMMUNICATION
MAIN
SUB
SW3-1
OFF (*)
ON
• Input Error Data: SW3-2
Hold: When the communication from an input module is lost
due to the input module error, the network module holds the
signal and stands by until the communication recovers.
Set to ‘0’: When the communication from an input module
is lost due to the input module error, the network module
outputs ‘0.’
SW
INPUT ERROR DATA
HOLD
SET ‘0’
SW3-2
OFF (*)
ON
• LED Function: SW3-4
Functions assigned to the front RUN and ERR LEDs can
be selected.
SW3-4
LED FUNCTION
RUN
ERR
OFF(*)
Green when normal
Green ON or blink-
ing when abnormal
ON
Red blinking when
receiving
Red blinking when
transmitting
Note: Be sure to set unused SW3-3 to OFF.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■
NETWORK MODULE SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Time (no communication time)
0.2 – 3200.0 (sec.)
3.0 (sec.)