INSTRUCTION MANUAL

T-Link INTERFACE MODULE

(Fuji Electric T-Link interface module equivalent)

MODEL

R3-NF2

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Network interface module ..................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

HOT SWAPPABLE MODULES

• The module can be replaced while the power is ON.  Be 

sure to replace it when the module is not communicat-
ing with a host, as it may affect the system.  Replacing 
multiple modules at once may greatly change line voltage 
levels.  We highly recommend to replace them one by one.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  100 – 120V AC rating: 85 – 132V, 47 – 66 Hz, approx. 20VA
  200 – 240V AC rating: 170 – 264V, 47 – 66 Hz, approx. 20VA

    24V DC rating: 24V ±10%, approx. 12W

 

GENERAL PRECAUTIONS

• DO NOT set the switches while the power is supplied.  

The switches are used only for maintenance without the 
power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables (power supply, input and output) 

close to noise sources (relay drive cable, high frequency 
line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

INSTALLATION

Use the Installation Base Model R3-BS, or Model R3-BSW 
for free I/O address capability.

Before mounting the Network Interface Module onto the 
Base, be sure to configure the module as explained below.

 

NODE ADDRESS

See “COMPONENT IDENTIFICATION.”

 

NETWORK SLOTS ON THE BASE

I/O 1

I/O 2

I/O n

With Model R3-BS base, mount the I/O Modules without 
any space between them from the left end (I/O 1) to the 
right in order that the Network Module assigns data areas 
from I/O 1.  If the I/O module 1 is not mounted, or there is 
any empty slot between the modules, communication error 
occurs.
Network Module(s) and Power Module are mounted basi-
cally at the right end though technically they could be 
mounted in any position.

With Model R3-BSW base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each 
module using rotary switches equipped on the base.