MODEL: MRP4

   (Sequential control signal suffix code B)
   M3 chromated steel
   (other terminal box types)
   (torque 0.5 N·m)
Housing material: Diecast aluminium
Drive: Stepping motor
Position detection: Potentiometer
Deadband: 0.1 – 4.5 % adjustable (factory set to 1.5 %)
Restarting timer: 0 – 10 sec. adjustable
(factory set to 1.5 sec.)
Isolation: AC power to signal
Zero adjustment: 0 – 25 %
Span adjustment: 50 - 100 %
Protective functions: Overload protection
Power indicator: Green LED turns on with power supplied.
Input indicator: Green LED turns on with normal input
Status indicator LED: Red light blinks in 2 sec. intervals in
normal operations; blinks in 0.5 sec. intervals when a
foreign object is detected mechanically caught inside.
Manual operation: Not available

INPUT SPECIFICATIONS

• DC Current: Input resistor incorporated (250 Ω)
• DC Voltage: 1 – 5 V DC or specific range within 0 – 5 V DC,
minimum span 1 V
(For a current input, convert the current to a voltage with
250 Ω)
Input resistance: Approx. 1 MΩ
• Forced open/close signal:
Dry contact inputs to command clockwise and
counterclockwise turns
Rating: 5 V DC @ 2.5 mA

OUTPUT SPECIFICATIONS

• Operation Time & Torque (at rated power voltage)
MRP4-x4: 7 sec. / 90°; torque 5 N·m (3.69 ft·lbs)
MRP4-x5: 13 sec. / 90°; torque 5 N·m (3.69 ft·lbs)
• Position Output: 1 – 5 V DC (not isolated)
With “direct” action, 5 – 1 V DC position output is provided
proportionally to 4 – 20 mA DC (1 – 5 V DC) input.
Load resistance: ≥ 5 kΩ
• Full-open / -closed signals: Limit switch contact
Rating: 125 V AC @ 0.75 A (cos ø = 1)
30 V DC @ 0.6 A (resistive load)
Mechanical life: 3 × 10

7

 cycles

Maximum operation frequency: 60 cycles/min.
• Full-closed/overload signal: Relay contact
Full-closed signal trips at approx. 2 % of span.
Rating: 250 V AC @ 1 A (cos ø = 1)
30 V DC @ 1 A (resistive load)

INSTALLATION

Power Consumption
•AC power input: Approx. 25 VA
•DC power input: Approx. 0.6 A
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: 0.5 G max.
Mounting position: All directions
Do not mount the actuator with its output stem or cable
connector on the upside if the actuator is to be exposed to
dripping water.
Weight
  DC powered: 1.1 kg (2.43 lbs)
  AC powered: 1.3 kg (2.87 lbs)
  Add 0.7 kg (1.54 lbs) for the terminal box.

PERFORMANCE

Resolution: 1/1000 or 0.09°, whichever is greater, with 0.1
% deadband setting
Insulation resistance
•AC powered: ≥ 100 MΩ with 500 V DC
(signal or metallic housing to power)
≥ 100 MΩ with 100 V DC
(signal to metallic housing)
•DC powered: ≥ 100 MΩ with 100 V DC
(signal or power to metallic housing)
Dielectric strength
•AC powered: 1500 V AC @ 1 minute
(signal or metallic housing to power)
100 V AC @ 1 minute
(signal to metallic housing)
•DC powered: 100 V AC @ 1 minute
(signal or power to metallic housing)

STANDARDS & APPROVALS

CE conformity:
EMC Directive (2004/108/EC)
  EMI EN 61000-6-4: 2007
  EMS EN 61000-6-2: 2005
Low Voltage Directive (2006/95/EC)
 EN 61010-1: 2001
 Measurement Category II
 Pollution Degree 2
 Full-open/-closed signal to other, power or metallic
 housing: Reinforced insulation (125 V)

TERMINOLOGY

• Overload (Lock) Protection
The Mini-Top Series is equipped with a protection circuit
against overload caused by for example the valve catching
an alien substance.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание MRP4

Страница 1: ...t A 4 20 mA DC Input resistance 250 Z Specify current See INPUT SPECIFICATIONS Voltage 6 1 5 V DC Input resistance approx 1 M 0 Specify voltage See INPUT SPECIFICATIONS 6 CE MARKING C With 0 Without 7...

Страница 2: ...n frequency 60 cycles min Full closed overload signal Relay contact Full closed signal trips at approx 2 of span Rating 250 V AC 1 A cos 1 30 V DC 1 A resistive load INSTALLATION Power Consumption AC...

Страница 3: ...ic limiters in order to prevent mechanical locks when the input goes below 0 or above 100 Limiters are set at approx 0 5 for the full closed side approx 100 5 for the full open side Full open closed s...

Страница 4: ...3 2 4 6 5 7 8 11 9 10 With Both Full open closed Signal and Forced Open Close Signal COM2 COM1 COM3 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 b...

Страница 5: ...4 23 91 42 1 65 43 1 69 35 1 38 60 2 36 110 4 33 150 5 91 98 3 86 90 3 54 130 5 12 2 08 127 5 167 6 57 17 67 10 0 043 sq 0 46 1 81 dia 4 M5 10 39 deep 2 G 1 2 CONDUIT YOKE SURFACE 36 0 1 dia 0 12 47 d...

Страница 6: ...CW CW RESTART TIMER DEADBAND ADJ MODE SELECTOR Motor Control Logic Motor Driver Hi Lo Limiter Input Circuit Position Output Switching Regulator POWER Power Circuit CCW CW FORCED OPEN CLOSE SIGNAL POWE...

Страница 7: ...ters 6 inches above the cover OUTDOOR USE When installing the MRP outdoor or where it is exposed to rain or water drops be sure to fasten the cable connector tightly and leave a slack of the cable Do...

Страница 8: ...life of the actuator FUSE A fuse is equipped for protection against overload current When you turn the power supply on check that the power LED is on If it is off check that the fuse is melted Replace...

Страница 9: ...rse Actions Operation at Abnormally Low Input Power Indicator green with power supplied Input Indicator green with input applied Status Indicator red blinks in 2 sec intervals blinks in 0 5 sec interv...

Страница 10: ...L MIN SPAN MAX SPAN MRP4 1 MRP5 1 45 90 MRP6 1 MRP4 2 90 180 MRP6 2 Standard Zero Position M i n i m u m s p a n M a x i m u m s p a n M a x i m u m O p e r a t i o n R a n g e 5 d e g 5 d e g Adjusta...

Страница 11: ...nal COM2 COM1 COM2 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 brown 8 FULL OPEN or FULL CLOSED SIGNAL output stem turned CCW output stem turned C...

Страница 12: ...The following explanation applies to reverse action For di rect action read the value in the brackets Remark Applying an over torque to the adjustments may destroy stoppers or other sections of them U...

Страница 13: ...nd Check input signal Narrow the deadband ON Flash 0 5 sec Actuator mechanism is damaged Repair Overload cause by a foreign object caught in the valve Check the valve Control PCB damaged Repair or rep...