R7K4FML3-6-DAC32B
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7773-E Rev.3 P. 5 / 11
■
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE
terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
36
19
20
28
V+
Y0
V-
Y15
+ −
1
5
10
2
6
4
7
13
8
9
14
12
15
11
16
17
18
COM
COM
X2
X4
X6
X8
X10
X12
X14
X1
X15
X3
X5
X7
X9
X11
X13
X0
3
6
7
24V DC
0V
3
FE
*
*
■
Input Connection Examples
MECHATROLINK
CONNECTOR
MECHATROLINK
CONNECTOR
*
MECHATROLINK connectors are internally connected.
The network cable can be connected to either one.
PNP Connection
1
10
X0
COM
–
+
X15
NPN Connection
1
10
X0
COM
–
+
X15
COM
COM
19
23
28
20
24
22
25
31
26
27
32
30
33
29
34
35
36
21
V
–
V+
Y18
Y20
Y22
Y24
Y26
Y28
Y30
Y17
Y31
Y19
Y21
Y23
Y25
Y27
Y29
Y16
2
18
■
Output Connection Examples
2
18
MOUNTING REQUIREMENTS
unit: mm (inch)
220 (8.66)
2–M4
WIRING INSTRUCTIONS
■
TORQUE
Wiring screw for separable terminal: 0.5 N∙m
Fixing screw for separable terminal: 0.5 N∙m
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd
6 (.24) max
3.3 (.13) max
mm (inch)
■
HOW TO UNMOUNT THE SEPARABLE TERMINAL
The separable terminal of the unit is 2 piece constructions.
It is possible to remove the terminal by loosening two screws
of terminal alternately.