MDR-8

P. 2 / 2

EM-8131  Rev.6

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

INSTALLATION

Refer to the figure below.

 

n

EXTERNAL DIMENSIONS  mm (inch)

P1

PROTECT

SIDE

SURGE

SIDE

S1

P2

S2

P3

S3

P4

S4

P5

S5

P6

S6

P7

S7

P8

S8

COM

COM

GND

GND

130 (5.12)

145 (5.71)

160 (6.30)

70 (2.76)

95 (3.74)

25 (.98)

40 (1.57)

4–4.5 (.18) dia.

MTG HOLE

20–M3 SCREW

•When mounting, no extra space is needed between units.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.
Be sure to cross-wire between the ground terminal (G) and 
that
of the protected equipment.

TELEMETER

PLC

XMTR

M-RESTER

PROTECTED

EQUIPMENT

M-RESTER

P1

P2

P8

G

COM

RELAY

METAL

HOUSING

FIELD

S1

S2

S8

COM

S1

S2

S8

G

G

COM

P1

P2

P8

COM

All negative lines are connected to COM.

M-RESTER

PROTECTED

EQUIPMENT

G

G

CROSSOVER WIRE

GROUNDING

(100 ohms or less)

A crossover wire between M-RESTER ground and the ground or 

metallic housing of the equipment is required for protection.

If the protected equipment has no ground terminal, ground the
M-RESTER only.

MAINTENANCE

Check M-RESTER periodically. Many cases of lightning are 
ignored, and even lightning at a far distance often causes 
inductive surges.  We recommend that you check your M-
RESTER about twice a year, before and after the rainy sea-
son. Check whenever you experience a strong lightning oc-
currence.  Checking procedure is explained in the following:

 

n

CHECKING

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the ground terminal (G) is connected to 

the metallic housing of protected equipment.

• Make sure that the ground terminal (G) is grounded to 

earth.

DISCHARGE ELEMENTS

Remove all wiring connected to M-RESTER when you test 
the discharge elements.

• Check resistance across the following terminals on the 

high resistance range of multimeter and confirm no con-
duction. (The meter will show 10MΩ or greater.)  Termi-
nals (P1) or (P2) or (P3) or (P4) or (P5) or (P6) or (P7) or 
(P8) – (COM), (COM) – (G)  When measuring across the 
Px – COM, apply the positive voltage to the Px terminal.

• Check that discharging occurs across the same terminals 

with a 500V DC/1000MΩ megger. (The megger will show 
20MΩ or less.)

• If any of the above tests shows negative, replace the M-

RESTER