WIRING INSTRUCTIONS
• Applicable wire size
Solid: 0.2 to 2.5 mm
2
(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm
2
(Tinning wire ends may
cause contact failure and therefore is not
recommended.)
Ferruled: 0.2 to 1.5 mm
2
(0.55 to 1.35 dia.)
• Expose wire conductors by 8 mm (0.31”).
8 mm
8 mm
3.7 mm dia.
max.
3.7 mm dia.
max.
Wire exposure
Recommended
ferruled wire
• How to Connect Wires
Screwdriver
Wire
Insert a wire. Confirm that the wire tip hits the bottom and
tighten the screw with a screwdriver.
Confirm that the wire’s insulation tube is not caught in the
terminal. (Torque: 0.3 N·m)
Screwdriver
Wire
8 mm
6 mm
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check that the input frequency is 30 Hz or less
for relay contact, 100 kHz or less for other types of input.
Check also that input pulse is 10 msec. or wider for relay
contact, 5 µsec. or wider for other types of input.
4) Output: Check that the load resistance meets the de-
scribed specifications as shown below.
OUTPUT
LOAD REQUIREMENTS
Open collector
50 V DC @ 100 mA max.
Voltage pulse
1.0 kΩ min. for 5 V
2.4 kΩ min. for 12 V
4.8 kΩ min. for 24 V
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.