background image

M3LT

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-2661-A  P. 2 / 7

COMPONENT IDENTIFICATION

Specifications
(side)

Body

SW Setting

 

HOW TO OPEN THE COVER WHEN SETTING DIP SW

Hold at the top and bottom of the unit as shown below and 
slide the housing cover gently to open until it hits the latch-
ing inside the unit.

• Housing Cover Fully Opened

Caution: 
Handle the cover carefully to protect internal components from damage.
DO NOT pull beyond where the housing cover is latched.  The plastic 
housing may be damaged.

 

HOW TO SEPARATE THE EURO TYPE CONNECTOR     

TERMINAL BLOCKS

When you need to separate the euro type connector termi-
nal blocks from the transmitter body for wiring, insert a mi-
nus driver between the euro type connector terminal block 
and the housing body, pull up the driver and pull out the 
euro type connector terminal block.

INSTALLATION

 

DIN RAIL MOUNTING

Set the unit so that its DIN rail adaptor is at the bottom.  
Position the upper hook at the rear side of the unit on the 
DIN rail and push in the lower.  When removing the unit, 
push down the DIN rail adaptor utilizing a minus screw-
driver and pull.

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

Содержание M3LT

Страница 1: ... must be mounted inside a panel Insert noise filters for the power source input and output connected to the unit COSEL Model NAC 04 472 TDK Model ZCAT 3035 1330 or equivalent is recommended Install lightning surge protectors for those wires connect ed to remote locations The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection ...

Страница 2: ...ere the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from the transmitter body for wiring insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALLATI...

Страница 3: ...erminal 5 The CJC Sensor is calibrated to a particular unit and not interchangeable with another Match the Serial No of the unit and the sensor WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5 mm2 Tinning wire ends may cause contact failure and therefore is not recommended Ferruled 0 2 to 1 5 mm2 0 55 to 1 35 dia The following Phoenix Contact termi...

Страница 4: ...moved Selectable I O type and ranges are listed in Table 8 and 9 DIP SW CONFIGURATION MODE Turn the SW2 8 OFF to enable the DIP SW Field Configu ration mode as shown in Table 1 See Table 3 to configure the input and Table 6 for the out put PC CONFIGURATION MODE Turn the SW2 8 ON to enable the PC Configuration mode as shown in Table 1 All programmable features can be set up on a PC regardless of ot...

Страница 5: ...the setup actions in each step of Calibration Modes Please read the following explanations referring to Calibration Flow Chart below CALIBRATION FLOW CHART POWER ON Amber LED Green LED Control Buttons Red LED OFF ON Blink RUN MODE LD2 LD3 A G RUN MODE LD2 LD3 G R LD1 LD2 LD3 LD1 LD2 LD3 0 INPUT CONFIGURED 100 INPUT CONFIGURED INPUT CALIBRATION MODE LD1 OUTPUT CALIBRATION MODE LD2 LD3 LD1 LD2 LD3 0...

Страница 6: ... LED is blinking ZERO SPAN ADJUSTMENTS After the transmitter is installed and operational fine zero and span tuning can be performed as explained below Both zero and span are adjustable within 15 1 Run Mode Confirm that the green LED is blinking model M3LT x A or the green LED turns on model M3LT x B 2 Fine Zero Calibration Mode Press MODE button for 1 or 2 seconds until the LD1 red LED is ON and ...

Страница 7: ... different blink ing patterns Examples are shown below LD1 LD2 LD3 A A A LD1 LD2 LD3 G LD1 LD2 LD3 G LD1 LD2 LD3 LD1 LD2 LD3 A LD1 LD2 LD3 A G G LD1 LD2 LD3 A G LD1 LD2 LD3 A A A R R R G NORMAL OPERATION RUN MODE ERROR MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 7 Burnout in PC Configura...