CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) DIP SW setting:  Check that the switches are set to ap-

propriate positions.

3) Power input voltage:  Check voltage across the terminal 

11 – 12 with a multimeter.

4) Input:  Check that the input signal is within 0 – 100% of 

full-scale.

  If the RTD wires are broken, the output goes over 100% 

(below 0% with downscale protection) due to burnout 

function.

  Confirm the status indicator LED pattern and check 

leadwires in such a case.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

I/O RANGING & FINE ADJUSTMENTS

After the DIP SW setting is complete, set up the precise 
input and output range using the front control buttons.  Be 
sure that the front control button function is enabled with 
the DIP switch setting.
After the DIP SW setting is complete, set up the precise 
input and output range using the front control buttons.
The front LEDs’ colors and blinking patterns help you to 
easily identify the transmitter’s status and confirm the set-
up actions in each step of Calibration Modes.  Please read 
the following explanations referring to “Calibration Flow 
Chart”.

 

PREPARATION (e.g. M3LR-R4/A)

1) Mount the DIP-SW-configured M3LR on to a DIN rail.
2) Connect the M3LR to a reference resistor and a multim-

eter and to a DC power source as shown below.

7

8

11

12

M3LR

Multimeter

+

DC Power Source

+ –

1

2

4

5

B

4-wire

RTD

A

A

B

3) Turn the power supply on and wait for 10 minutes.

 

INPUT & OUTPUT RANGING

[Example] Setting the input to Pt 100, 0 – 100°C and the 
output to 1 – 5 V DC

1) Run Mode: Confirm that the green LED is blinking (mod-

el M3LR-x/A) or the green LED turns on (model M3LR-

x/B).

2) Input Ranging Mode: Hold down MODE button for longer 

than 5 seconds until the LD1 red LED is ON and the LD2 

red LED is blinking.

3) 0% Input Ranging: Apply the desired minimum input lev-

el (e.g. 100 Ω) from the reference resistor and hold down 

DOWN button until the LD1 blinks for approx. 2 sec. and 

then turns OFF.  When you release the button, the LD1 is 

returned to ON.

  The blinking LD1 means that the value is stored in the 

memory.  If the LED does not change, the entered level 

may be inappropriate: too small a span, or out of usable 

range (same for all steps).

4) 100% Input Ranging: Apply the desired maximum input 

level (e.g. 138.5 Ω) from the reference resistor and hold 

down UP button until the LD1 blinks for approx. 2 sec. 

and then turns OFF.  When you release the button, the 

LD1 is returned to ON.

5) Output Ranging Mode: Press MODE button and confirm 

that the LD3 red LED instead of LD2 is blinking.

6) 0% Output Ranging: Increase or decrease the simulated 

input until the meter shows the desired minimum output 

level (e.g. 1 V).  Hold down DOWN button until the LD1 

blinks for approx. 2 sec. and then turns OFF.  When you 

release the button, the LD1 is returned to ON.

7) 100% Output Ranging: Increase or decrease the simu-

lated input until the meter shows the desired maximum 

output level (e.g. 5 V).  Hold down UP button until the 

LD1 blinks for approx. 2 sec. and then turns OFF.  When 

you release the button, the LD1 is returned to ON.

8) Run Mode: When calibration is completed, press MODE 

button once and confirm that: the LD1 green LED is 

blinking in case of M3LR-x/A; and the LD1 green LED is 

ON in case of M3LR-x/B.

Содержание M3LR

Страница 1: ...nected to the unit COSEL Model NAC 04 472 TDK Model ZCAT 3035 1330 or equivalent is recommended The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measur...

Страница 2: ... where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from the transmitter body for wiring insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALL...

Страница 3: ...RAM CONFIGURATOR JACK 7 8 11 12 OUTPUT POWER 2 4 1 5 B 2 wire RTD 3 wire RTD 4 wire RTD A A B B A B A B WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5 mm2 Tinning wire ends may cause contact failure and therefore is not recommended Ferruled 0 2 to 1 5 mm2 0 55 to 1 35 dia The following Phoenix Contact terminals are recommended AI 0 25 8YE 0 2 to ...

Страница 4: ...ctable I O type and ranges are listed in Table 8 and 9 DIP SW CONFIGURATION MODE Turn the SW2 8 OFF to enable the DIP SW Field Configu ration mode as shown in Table 1 See Table 3 to configure the input and Table 6 for the out put PC CONFIGURATION MODE Turn the SW2 8 ON to enable the PC Configuration mode as shown in Table 1 All programmable features can be set up on a PC regardless of other DIP SW...

Страница 5: ...o 1562 328 to 1562 0 27 0 27 0 27 Pt 400 Pt 500 Pt 1000 20 20 20 200 to 850 200 to 850 200 to 850 0 15 0 15 0 15 36 36 36 328 to 1562 328 to 1562 328 to 1562 0 27 0 27 0 27 Pt 50 Ω JIS 81 JPt 100 JIS 89 Ni 100 20 20 20 200 to 649 200 to 510 80 to 260 0 15 0 15 0 15 36 36 36 328 to 1200 328 to 950 112 to 500 0 27 0 27 0 27 Ni 120 Ni 508 4 Ω Ni Fe 604 Cu 10 25 C 20 20 20 20 80 to 260 50 to 200 200 t...

Страница 6: ...nd wait for 10 minutes INPUT OUTPUT RANGING Example Setting the input to Pt 100 0 100 C and the output to 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LR x A or the green LED turns on model M3LR x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1 red LED is ON and the LD2 red LED is blinking 3 0 Input Ranging Apply the desired minimum input...

Страница 7: ...tput ranges keep pressing UP or DOWN button until the LD1 blinks for approx 2 seconds and turns off which indicates the setup is complete If the LED does not change the entered level may be inappropriate e g out of usable range For the model M3LR x A the green LED is blinking For the model M3LR x B the green LED turns on FINE ZERO ADJUSTMENT MODE UP or DOWN FINE SPAN ADJUSTMENT MODE UP or DOWN App...

Страница 8: ...entering values for multiple times within one step of Calibration Mode Signal level is stored each time the respective UP or DOWN button is pressed I O RANGE LABEL Blank I O range labels are included in the product package Write in the configured ranges and put the label on the side as shown below INPUT OUTPUT I O Range Label included in the product package STATUS INDICATOR LED Combinations of the...

Отзывы: