CALIBRATION FLOW CHART

POWER ON

Amber LED

Green LED

Control
Buttons

Red LED

OFF

ON

Blink

RUN MODE

LD2

LD3

A

G

RUN MODE

LD2

LD3

G

R

LD1

LD2

LD3

LD1

LD2

LD3

0% INPUT

CONFIGURED

100% INPUT

CONFIGURED

INPUT

RANGING

MODE

LD1

OUTPUT

RANGING

MODE

LD2

LD3

LD1

LD2

LD3

0% OUTPUT

CONFIGURED

100% OUTPUT

CONFIGURED

G

G

R

R

R

R

G

R

R

G

Fine Adjustments ?

I/O Ranging ?

HOLD DOWN  

MODE

 

 1 – 2 s

HOLD DOWN  

MODE

 

 > 5s

PRESS  

MODE

PRESS  

MODE

PRESS  

MODE

PRESS  

MODE

HOLD DOWN

DOWN

HOLD DOWN

UP

DOWN

UP

MODE

HOLD DOWN

DOWN

HOLD DOWN

UP

When you set 0% or 100% input/output ranges, 
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off, 
which indicates the setup is complete.
If the LED does not change, the entered level may
be inappropriate: e.g. out of usable range.

*

For the model M3LR-x/A, the green LED is blinking.  

  For the model M3LR-x/B, the green LED turns on.

FINE ZERO

ADJUSTMENT MODE

UP

  or  

DOWN

FINE SPAN

ADJUSTMENT MODE

UP

  or  

DOWN

Apply simulated 0% input signal.

Apply simulated 100% input signal.

Adjust simulated input until the output meter 
shows desired 0% output.

Adjust simulated input until the output meter 
shows desired 100% output.

Once the transmitter
enters the fine zero
adjustment mode, 
the output goes to 
preadjusted 0% 
value regardless 
of the present input 
signal.

Once the transmitter
enters the fine span
adjustment mode, 
the output goes to 
preadjusted 100% 
value regardless 
of the present input 
signal.

LD1

*

LD1

*

Содержание M3LR

Страница 1: ...nected to the unit COSEL Model NAC 04 472 TDK Model ZCAT 3035 1330 or equivalent is recommended The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measur...

Страница 2: ... where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from the transmitter body for wiring insert a mi nus driver between the euro type connector terminal block and the housing body pull up the driver and pull out the euro type connector terminal block INSTALL...

Страница 3: ...RAM CONFIGURATOR JACK 7 8 11 12 OUTPUT POWER 2 4 1 5 B 2 wire RTD 3 wire RTD 4 wire RTD A A B B A B A B WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5 mm2 Tinning wire ends may cause contact failure and therefore is not recommended Ferruled 0 2 to 1 5 mm2 0 55 to 1 35 dia The following Phoenix Contact terminals are recommended AI 0 25 8YE 0 2 to ...

Страница 4: ...ctable I O type and ranges are listed in Table 8 and 9 DIP SW CONFIGURATION MODE Turn the SW2 8 OFF to enable the DIP SW Field Configu ration mode as shown in Table 1 See Table 3 to configure the input and Table 6 for the out put PC CONFIGURATION MODE Turn the SW2 8 ON to enable the PC Configuration mode as shown in Table 1 All programmable features can be set up on a PC regardless of other DIP SW...

Страница 5: ...o 1562 328 to 1562 0 27 0 27 0 27 Pt 400 Pt 500 Pt 1000 20 20 20 200 to 850 200 to 850 200 to 850 0 15 0 15 0 15 36 36 36 328 to 1562 328 to 1562 328 to 1562 0 27 0 27 0 27 Pt 50 Ω JIS 81 JPt 100 JIS 89 Ni 100 20 20 20 200 to 649 200 to 510 80 to 260 0 15 0 15 0 15 36 36 36 328 to 1200 328 to 950 112 to 500 0 27 0 27 0 27 Ni 120 Ni 508 4 Ω Ni Fe 604 Cu 10 25 C 20 20 20 20 80 to 260 50 to 200 200 t...

Страница 6: ...nd wait for 10 minutes INPUT OUTPUT RANGING Example Setting the input to Pt 100 0 100 C and the output to 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LR x A or the green LED turns on model M3LR x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1 red LED is ON and the LD2 red LED is blinking 3 0 Input Ranging Apply the desired minimum input...

Страница 7: ...tput ranges keep pressing UP or DOWN button until the LD1 blinks for approx 2 seconds and turns off which indicates the setup is complete If the LED does not change the entered level may be inappropriate e g out of usable range For the model M3LR x A the green LED is blinking For the model M3LR x B the green LED turns on FINE ZERO ADJUSTMENT MODE UP or DOWN FINE SPAN ADJUSTMENT MODE UP or DOWN App...

Страница 8: ...entering values for multiple times within one step of Calibration Mode Signal level is stored each time the respective UP or DOWN button is pressed I O RANGE LABEL Blank I O range labels are included in the product package Write in the configured ranges and put the label on the side as shown below INPUT OUTPUT I O Range Label included in the product package STATUS INDICATOR LED Combinations of the...

Отзывы: