COMPONENT IDENTIFICATION

Body

SW Setting

Specifications
(side)

 

HOW TO OPEN THE COVER WHEN SETTING DIP SW

Hold at the top and bottom of the unit as shown below and 
slide the housing cover gently to open until it hits the latch-
ing inside the unit.

• Housing Cover Fully Opened

Caution: 
Handle the cover carefully to protect internal components from damage.
DO NOT pull beyond where the housing cover is latched.  The plastic 
housing may be damaged.

 

  HOW TO SEPARATE THE EURO TYPE CONNECTOR 

TERMINAL BLOCKS

When you need to separate the euro type connector termi-
nal blocks from the transmitter body for wiring, insert a mi-
nus driver between the euro type connector terminal block 
and the housing body, pull up the driver and pull out the 
euro type connector terminal block.

INSTALLATION

 

DIN RAIL MOUNTING

Set the unit so that its DIN rail adaptor is at the bottom.  
Position the upper hook at the rear side of the unit on the 
DIN rail and push in the lower.  When removing the unit, 
push down the DIN rail adaptor utilizing a minus screw-
driver and pull.

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

Содержание M3LM

Страница 1: ...472 TDK Model ZCAT 3035 1330 or equivalent is recommended The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this...

Страница 2: ...where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from th...

Страница 3: ...NECTION DIAGRAM CONFIGURATOR JACK 7 8 11 12 OUTPUT POWER 4 5 1 3 2 1 POTENTIOMETER max min WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5 mm2 Tinnin...

Страница 4: ...type and ranges are listed in Table 7 and 8 DIP SW CONFIGURATION MODE Turn the SW2 8 OFF to enable the DIP SW Field Configuration mode as shown in Table 1 See Table 3 to configure the input and Table...

Страница 5: ...o 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LM x A or the green LED turns on model M3LM x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1...

Страница 6: ...nk RUN MODE LD2 LD3 A G RUN MODE LD2 LD3 G R LD1 LD2 LD3 LD1 LD2 LD3 0 INPUT CONFIGURED 100 INPUT CONFIGURED INPUT RANGING MODE LD1 OUTPUT RANGING MODE LD2 LD3 LD1 LD2 LD3 0 OUTPUT CONFIGURED 100 OUTP...

Страница 7: ...ERROR MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 6 Burnout in PC Configuration Mode Op...