manualshive.com logo in svg
background image

M3LM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-2663-A  Rev.3  P. 4 / 7

EXTERNAL & INTERNAL VIEWS

Configuration DIP SW

8

SW2

SW1

SW3

7 6 5 4 3 2 1

ON

OFF

ON

OFF

4 3 2 1

ON

OFF

4 3 2 1

10 11 12

7

8

9

4

5

6

1

2

3

Configurator Jack

DOWN Button

UP Button

MODE Button

LED3 (LD3)

LED2 (LD2)

LED1 (LD1)

FRONT VIEW

■ 

SIDE VIEW

For M3LM-R4/A, the DIP switch setting is required to select output types before setting a precise output range using the PC 
configurator software.

CONFIGURATION MODE & DIP SW SETTINGS

When you program the transmitter module, two configuration modes are available: Field Configuration using DIP SW / con-
trol buttons, and PC Software. (The Option B type is for the field configuration only.)
The internal DIP switches are used to configure input and output type.  Once the module is configured, precise ranges are 
set up with the front control buttons using a simulator connected to the input terminals and a multimeter connected to the 
output terminals as a reference.
The calibrated input and output ranges are stored in the internal memory.  The module reads the DIP-switch-calibrated con-
figuration only once after the power supply is turned on.  Set the switches with the power supply removed.
Selectable I/O type and ranges are listed in Table 7 and 8.

 

DIP SW CONFIGURATION MODE

Turn the SW2-8 OFF to enable the DIP SW (Field Configuration) mode as shown in Table 1.
See Table 3 to configure the input and Table 5 for the output.

 

PC CONFIGURATION MODE

Turn the SW2-8 ON to enable the PC Configuration mode as shown in Table 1.  All programmable features can be set up on 
a PC regardless of other DIP SW setting except that the output type must be selected with the DIP SW1-1 through SW1-4 
(See Table 6).
For detailed information on the PC configuration, refer to the M3CFG instruction manual.

 

CONFIGURATION MODE (SW2) 

Table 1

MODE

SW2-8

Configuration mode can be Confirmed 
with the front LED.

DIP SW

PC

OFF

ON

 

FRONT CONTROL BUTTON LOCK (SW2) 

Table 2

Table 2 setting is applicable to firmware version 2.02 or 
higher (marking on the product).

LOCK

SW2-1

PC Configuration is not disabled when 
the front control button function is 
locked.

Unlock

Lock

OFF

ON

 

POTENTIOMETER (SW2) 

Table 3

RESISTANCE

SW2-7

SW2-6

SW2-5

SW2-4

0 – 20 kΩ
0 – 1000 Ω
0 – 400 Ω

OFF
OFF
OFF

OFF
OFF
OFF

OFF
OFF

ON

ON

OFF
OFF

0 – 200 Ω
0 – 90 Ω

OFF
OFF

OFF

ON

ON

OFF

ON

OFF

 

BURNOUT (SW3) 

Table 4

BURNOUT

SW3-2

SW3-1

No burnout

Upscale

Downscale

OFF
OFF

ON

ON

OFF
OFF

 

OUTPUT TYPE (SW2 & 1) 

Table 5

OUTPUT

SW2-3 SW2-2 SW1-4 SW1-3 SW1-2 SW1-1

0 – 20 mA
-2.5 – +2.5 V
-10 – +10 V

OFF
OFF

ON

OFF

ON

OFF

OFF

ON
ON

ON

OFF
OFF

OFF
OFF

ON

OFF

ON

OFF

 

OUTPUT TYPE / PC CONFIG (SW1) 

Table 6

OUTPUT

SW1-4

SW1-3

SW1-2

SW1-1

0 – 20 mA
-2.5 – +2.5 V
-10 – +10 V

OFF

ON
ON

ON

OFF
OFF

OFF
OFF

ON

OFF

ON

OFF

Содержание M3LM

Страница 1: ...472 TDK Model ZCAT 3035 1330 or equivalent is recommended The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this...

Страница 2: ...where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from th...

Страница 3: ...NECTION DIAGRAM CONFIGURATOR JACK 7 8 11 12 OUTPUT POWER 4 5 1 3 2 1 POTENTIOMETER max min WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5 mm2 Tinnin...

Страница 4: ...type and ranges are listed in Table 7 and 8 DIP SW CONFIGURATION MODE Turn the SW2 8 OFF to enable the DIP SW Field Configuration mode as shown in Table 1 See Table 3 to configure the input and Table...

Страница 5: ...o 1 5 V DC 1 Run Mode Confirm that the green LED is blinking mod el M3LM x A or the green LED turns on model M3LM x B 2 Input Ranging Mode Hold down MODE button for longer than 5 seconds until the LD1...

Страница 6: ...nk RUN MODE LD2 LD3 A G RUN MODE LD2 LD3 G R LD1 LD2 LD3 LD1 LD2 LD3 0 INPUT CONFIGURED 100 INPUT CONFIGURED INPUT RANGING MODE LD1 OUTPUT RANGING MODE LD2 LD3 LD1 LD2 LD3 0 OUTPUT CONFIGURED 100 OUTP...

Страница 7: ...ERROR MODE System Error Indicates the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 6 Burnout in PC Configuration Mode Op...