M2XRP2

P. 4 / 5

EM-5059 Rev.5

ADJUSTING DETECTING LEVEL

  (voltage pulse, two-wire current pulse only)

Appropriate detecting level is determined according to the low chart below.

START

Confirm the Sensitivity Scale in the table 
below.
Assign the value in the following equation.

Detecting Level (V) = 
       DC Offset (V)

*

1

 

×

 Sensitivity Scale 

Set DIP SW to the DC coupling and adjust 
the detecting level to the value calculated 
above.
Set to 4V when the calculation result is 
higher than 4V, set to -2V when it is lower 
than -2V.

Adjust the detecting level 
appropriate for the sensor 
excitation voltage.

Adjust the detecting level 
to 0V appropriate for RS-
422 line driver pulse input.

Set DIP SW to the capacitor 
coupling and adjust the 
detecting level to 0V.

Voltage pulse input?

No

No

No

Yes

DC coupled input sensing?

Yes

Open collector input?

Yes

*

1. Rounded off to one decimal place.

Excitation
12V DC
5V DC

Detect. Level
2V
1V

• Setting Examples
Voltage Input (DC Offset = Pulse Amplitude / 2)

 

PULSE 

AMPLITUDE 

DETECTING 

  AMPLITUDE (Vp-p) 

RANGE (Vp-p) 

LEVEL (V)

 

30 

10 – 30 

2.5 

 

 

25 

10 – 30 

2.1 

 

 

15 

10 – 30 

1.3

 

10 

5 – 10 

2.5 

 

 

7.5 

5 – 10 

1.9

 

1 – 5 

2.5 

 

 

3.5 

1 – 5 

1.8 

 

 

1 – 5 

1

 

0.1 – 1 

2.5 

 

 

0.5 

0.1 – 1 

1.3

 DETECTING LEVEL

When the parameters have been set with DIP switches and 
the  PC  Conigurator  Software  (model:  JXCON),  a  speciic 
sensitivity scale is applied according to the pulse amplitude 
setting.   The  scaled  input  voltage  is  then  compared  to  the 
preset detecting level (-2.00 to +4.00V).
With  DC  coupling,  the  scaled  maximum  voltage  must  be 
higher  than  the  detecting  level  and  the  minimum  voltage 
must be lower than that so that the pulse state is accurately 
detected.  (Refer to the instruction manual for detailed in-
formation about adjusting the detecting level.)

• Maximum Frequency Range, Pulse Amplitude

INPUT 

MAX. FREQ. RANGE  MIN / MAX. AMPLITUDE

Open collector 

0 – 100 kHz 

5V / 12V

Voltage pulse 

0 – 100 kHz 

0.1 V / 30V

RS-422 line driver 

0 – 100 kHz 

----

• Sensitivity Scale

  PULSE AMPLITUDE 

MAX. INPUT  

SENSITIVITY 

 

RANGE 

VOLTAGE 

SCALE

 

10 – 30 Vp-p 

30V 

1 / 6

 

5 – 10 Vp-p 

10V 

1 / 2

 

1 – 5 Vp-p 

  5V 

1

 

0.1 – 1 Vp-p *

1

 

  1V 

5

*1. Input frequency within ±50 kHz