Operating instructions 

Temperature transmitter with display

TDxxxx

80234348 / 00    12 / 2015

UK

Summary of Contents for Elector 600

Page 1: ...Operating instructions Temperature transmitter with display TDxxxx 80234348 00 12 2015 UK ...

Page 2: ... Units with G sealing cone type TD25xx 5 6 Electrical connection 6 7 Operating and display elements 7 8 Parameter setting 7 8 1 IO Link 7 8 1 1 General information 7 8 1 2 Device specific information 7 8 1 3 Parameter setting tools 8 8 2 Adjustable parameters 8 9 Operation 8 10 Technical data 9 10 1 Temperature resistance 9 11 Factory setting 9 ...

Page 3: ...anted effects in your application That is why installation electrical connec tion set up operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator In order to guarantee the correct condition of the device for the operating time the device must only be used in media to which the wetted parts are sufficiently resistant Technical data The...

Page 4: ...uring range scaled at OU I MAW MEW 20 6 20 4 3 7 T C F I mA I mA T C F MEW MAW AEP ASP 20 6 20 4 3 7 MAW initial value of the measuring range MEW final value of the measuring range ASP analogue start point AEP analogue end point Within the measuring range the output signal is between 4 and 20 mA If the tem perature value is outside the limits of the measuring range the following output signal is p...

Page 5: ... lubricating paste which is suitable and approved for the application Use in hygienic areas to 3A requirements Make sure that the sensors are integrated into the system in accordance with 3A 5 1 Units with G sealing cone type TD25xx Tightening torque 30 50 Nm About sensor installation conforming to 3A Insert PEEK sealing ring E43911 Carry out installation according to separate installation instruc...

Page 6: ...n of electrical equipment must be adhered to Voltage supply according to EN 50178 SELV PELV Disconnect power Connect the unit as follows 4 3 2 1 L L 3 1 4 2 IO Link L L 1 2 1 2 Operation as 2 wire unit 1 Pin 1 L Pin 2 Analogue signal for temperature Operation as 4 wire unit 2 Pin 1 L Pin 2 Analogue signal for temperature Pin 3 L pin 4 IO Link ...

Page 7: ...n interface which requires an IO Link capa ble module IO Link master for operation The IO Link interface enables direct access to the process and diagnostic data and provides the possibility to set the parameters of the unit during operation In addition communication is possible via a point to point connection with a USB adapter cable You will find more detailed information about IO Link at www if...

Page 8: ...sured value 0 is shifted by this value FOU2 Behaviour of the output in case of an internal fault ON the analogue signal goes to the upper end stop value 21 1 mA OFF the analogue signal goes to the lower end stop value 3 5 mA Uni Unit of measurement for system temperature C or F Update rate of display d1 update of the measured values every 50 ms d2 update of the measured values every 200 ms d3 upda...

Page 9: ...ending on the medium temperature Further technical data and scale drawing at www ifm com 11 Factory setting Factory setting User setting OU I COF 0 0 FOU OFF Factory settings for the parameters ASP2 AEP2 and Uni technical data sheet at www ifm com More information at www ifm com ...