COMPONENT IDENTIFICATION

A. Measured Value (PV) / 

Alarm SET1 Display

B. Measured Value (PV)

Indicator LED

D. SELECT Key

C. Alarm SET2 / Parameter Display

J. Alarm SET2 Indicator LED

H. Alarm SET1 Indicator LED

G. Power Indicator LED

F. DOWN Key

E. UP Key

Ref.

Component Name

Function

A

Measured Value (PV) / Alarm SET1 Display Displaying either of Measured Value (PV) or Alarm Setpoint Value (SET1)

B

Measured Value (PV) Indicator LED

LED turns on when the Measured Value (PV) is displayed.

C

Alarm SET2 / Parameter Display

Displaying either of Alarm Setpoint Value (SET2) or parameter type code.

D

SELECT Key

Used for confirming current setpoints and switching between parameter 
blocks.

E

UP Key

Pressing the key increases display values.
They change continuously when it is kept pressed.

F

DOWN Key

Pressing the key decreases display values.
They change continuously when it is kept pressed.

G

Power Indicator LED

LED turns on while the power is turned on.

H

Alarm SET1 Indicator LED

LED turns on when the Alarm SET1 is in tripped conditions.

I

Alarm SET2 Indicator LED

LED turns on when the Alarm SET2 is in tripped conditions.

PREPARING POWER-UP

When the power is turned on, the unit displays all segments 
on the Measured Value (PV)/Alarm Setpoint Value (SET1) 
Display and on the Alarm Setpoint Value (SET2)/Parameter 
Display before starting operation.
To ensure a proper operation of the unit, set the parameters 
before starting up according to the operating conditions.
Be sure to remove power of the final control element before 
parameters setting.
Wait for 10 minutes for warming up the unit before its tem-
perature is stabilized and measuring is started.

HOW TO SET PARAMETERS

 

CONFIRMING CURRENT MEASURED VALUE AND 

ALARM SETPOINT VALUES

Pressing SEL key turns the display in order of SET1, SET2, 
PV, and blank.

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)*

2

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Press the key once.

Display pattern 2
Upper = PV (value)
Lower = blank

SEL

Press the key once.

Display pattern 3
Upper = blank
Lower = blank

SEL

Press the key once.

Returning to Display 
pattern 1

*2.  Which display pattern is to be displayed first after the 

power is turned on can be programmed in Parameter block 
1.

 

REGISTERING SETTING

1) Data is registered automatically in 3 seconds after the 

data is set.  Pressing SEL key also register the data.

2) The display automatically returns to the display pattern 

preset by PTn parameter when the unit is left for approx. 

30 seconds with no access.

Содержание KS2TR2

Страница 1: ...H Rapid temperature change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure to air containing heavy dust particles salt chemical components or iron particles Interference by static and magnetic noise Direct sunlight Heat accumulated by radiation or such 2 Mount...

Страница 2: ...DIAGRAM B B A 7 8 10 11 9 2 3 1 4 5 6 N C N O COM SET1 N C N O COM SET2 U V POWER RTD THERMOCOUPLE comp leadwire T C PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the top and bottom of the unit for separate the body from the base socket DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bot tom Position the upper hoo...

Страница 3: ... SET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SET2 Parameter Display before starting operation To ensure a proper operation of the unit set the parameters before starting up according to the operating conditions Be sure to remove power of the fin...

Страница 4: ...unit P d1 1 Seconds 1 to 999 Switching delay timer for SET1 P d2 1 Seconds 1 to 999 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 5 0 to 900 0 7 Time constant for the input filter CJM ON ON OFF ON OFF Cold junction compensation ADJ0 0 Deviative engineering unit 6 50 to 50 FS User s ZERO adjustment ADJS 0 Deviative engineering unit 6 50 to 50 FS User s SPAN adjustment P d0 0 Seconds 0 to 20 P...

Страница 5: ...es Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower 100 UP DOWN Press the keys until the display indicates 50 New value is registered if the unit is not accessed for 3 seconds Upper blank Lower 50 SEL Press the key once The lower display indicates t...

Страница 6: ...setting Upper blank Lower 3 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower 2 SEL Press the key once The lower display indicates the param eter name P n2 again Upper blank Lower P n2 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 2 Upper PV Lower blank Scaling P SL P SU ...

Страница 7: ...ew value is registered if the unit is not accessed for 3 seconds Upper blank Lower H SEL Press the key once The lower display indicates the param eter name bUrn again Upper blank Lower bUrn SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint Temperature unit Example Changing temperature unit P F from C to F Key Status o...

Страница 8: ...ndicates Pat tern 2 Pattern 3 and Parameter block 1 2 until P dF is on the display Upper blank Lower P dF DOWN Press the key twice Next parameter name is displayed Upper blank Lower ADJ0 SEL Press the key once ADJ0 is replaced with current setting Upper blank Lower 0 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower...

Страница 9: ... 4172 N N ALARM MODE v s PARAMETER CODE NO Param code P A1 P A2 Alarm modes Trip operation Set value Latching hold 9 Relay LED behavior in tripped conditions 0 No alarm 1 High Absolute value Without LED ON Coil energized 2 Low Absolute value Without LED ON Coil energized 3 High Absolute value With LED ON Coil energized 4 Low Absolute value With LED ON Coil energized 5 High Absolute value Without L...

Страница 10: ... info m system co jp EM 3606 Rev 5 P 10 10 CHARACTER SET 0 1 2 4 3 5 6 7 9 8 A B D C E F G I H J K L N M O P Q S R T U V W X Z Y LIGHTNING SURGE PROTECTION M System offers a series of lightning surge protector for protection against induced lightning surges Please contact M System to choose appropriate models ...

Отзывы: