HOW TO SET PARAMETER BLOCK 1

Press SEL key for 3 seconds until the display turns to the setting mode for Parameter block 1.

Alarm SET 1 parameter
[Example]

Changing alarm setpoint (ST1) for SET1 from 100 to 200.

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Keep pressing the key for 3 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3.

Upper = blank
Lower = ST1

SEL

Press the key once.

ST1 is replaced with current setting.

Upper = blank
Lower = 100

UP

DOWN

Press the keys until the display indicates 200.
tes 200. (New value is registered if the unit 
is not accessed for 3 seconds.)

Upper = blank
Lower = 200

SEL

Press the key once.

The lower display indicates the param-

eter name (ST1) again.

Upper = blank
Lower = ST1

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

Alarm SET 2 parameter
[Example]

Changing alarm setpoint (ST2) for SET2 from 100 to 50.

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Keep pressing the key for 3 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3.

Upper = blank
Lower = ST1

DOWN Press the key once.

Next parameter name is displayed.

Upper = black
Lower = ST2

SEL

Press the key once.

ST2 is replaced with current setting.

Upper = blank
Lower = 100

UP

DOWN

Press the keys until the display indicates 50.
(New value is registered if the unit is not 
accessed for 3 seconds.)

Upper = blank
Lower = 50

SEL

Press the key once.

The lower display indicates the param-

eter name (ST2) again.

Upper = blank
Lower = ST2

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

Display pattern

Selecting which display pattern should be indicated first 
after the power is turned on, or when the unit returns to 
display mode from setting mode.

[Example]

 Changing display pattern (PTn) 1 to 3.

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Keep pressing the key for 3 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3.

Upper = blank
Lower = ST1

DOWN Press the key twice.

Next parameter name is displayed.

Upper = blank
Lower = PTn

SEL

Press the key once.

PTn is replaced with current setting.

Upper = blank
Lower = 1

UP

DOWN

Press the keys until the display indicates 3.
(New value is registered if the unit is not 
accessed for 3 seconds.)

Upper = blank
Lower = 3

SEL

Press the key once.

The lower display indicates the param-

eter name (PTn) again.

Upper = blank
Lower = PTn

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 3
Upper = blank
Lower = blank

Содержание KS2TR2

Страница 1: ...H Rapid temperature change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure to air containing heavy dust particles salt chemical components or iron particles Interference by static and magnetic noise Direct sunlight Heat accumulated by radiation or such 2 Mount...

Страница 2: ...DIAGRAM B B A 7 8 10 11 9 2 3 1 4 5 6 N C N O COM SET1 N C N O COM SET2 U V POWER RTD THERMOCOUPLE comp leadwire T C PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the top and bottom of the unit for separate the body from the base socket DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bot tom Position the upper hoo...

Страница 3: ... SET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SET2 Parameter Display before starting operation To ensure a proper operation of the unit set the parameters before starting up according to the operating conditions Be sure to remove power of the fin...

Страница 4: ...unit P d1 1 Seconds 1 to 999 Switching delay timer for SET1 P d2 1 Seconds 1 to 999 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 5 0 to 900 0 7 Time constant for the input filter CJM ON ON OFF ON OFF Cold junction compensation ADJ0 0 Deviative engineering unit 6 50 to 50 FS User s ZERO adjustment ADJS 0 Deviative engineering unit 6 50 to 50 FS User s SPAN adjustment P d0 0 Seconds 0 to 20 P...

Страница 5: ...es Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower 100 UP DOWN Press the keys until the display indicates 50 New value is registered if the unit is not accessed for 3 seconds Upper blank Lower 50 SEL Press the key once The lower display indicates t...

Страница 6: ...setting Upper blank Lower 3 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower 2 SEL Press the key once The lower display indicates the param eter name P n2 again Upper blank Lower P n2 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 2 Upper PV Lower blank Scaling P SL P SU ...

Страница 7: ...ew value is registered if the unit is not accessed for 3 seconds Upper blank Lower H SEL Press the key once The lower display indicates the param eter name bUrn again Upper blank Lower bUrn SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint Temperature unit Example Changing temperature unit P F from C to F Key Status o...

Страница 8: ...ndicates Pat tern 2 Pattern 3 and Parameter block 1 2 until P dF is on the display Upper blank Lower P dF DOWN Press the key twice Next parameter name is displayed Upper blank Lower ADJ0 SEL Press the key once ADJ0 is replaced with current setting Upper blank Lower 0 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower...

Страница 9: ... 4172 N N ALARM MODE v s PARAMETER CODE NO Param code P A1 P A2 Alarm modes Trip operation Set value Latching hold 9 Relay LED behavior in tripped conditions 0 No alarm 1 High Absolute value Without LED ON Coil energized 2 Low Absolute value Without LED ON Coil energized 3 High Absolute value With LED ON Coil energized 4 Low Absolute value With LED ON Coil energized 5 High Absolute value Without L...

Страница 10: ... info m system co jp EM 3606 Rev 5 P 10 10 CHARACTER SET 0 1 2 4 3 5 6 7 9 8 A B D C E F G I H J K L N M O P Q S R T U V W X Z Y LIGHTNING SURGE PROTECTION M System offers a series of lightning surge protector for protection against induced lightning surges Please contact M System to choose appropriate models ...

Отзывы: