DIFFERENCES BETWEEN JB AND JB2/A

Means to back up the output value is different.
  JB: STATIC RAM (A large capacitance capacitor holds the value until the capacitor is discharged)
  JB2/A: E

2

PROM (Output value is stored at E

2

PROM and held until the next rewrite) 

JB: When power recovers during MAN control mode, the output value is different depending on the power fail period.
JB2/A: The output value at power recovery is selectable with ITEM 31.  Refer to the following table.

OUTPUT VALUE AT POWER RECOVERY DURING “MAN” CONTROL MODE

JB

Output value at the moment of power failure 
(recovery within the memory time)

Fixed value (recovery after the memory time)

JB2/A

ITEM 31 : 0

ITEM 31 : 1

 

COMPATIBILITY BETWEEN JB2 AND JB2/A

For JB2/A, the operation at power recovery is selectable (ITEM 30, 31).
When JB2 (without “/A”) is replaced with JB2/A compatibly, set JB2/A according to the ITEM 21 value of JB2 as following.

• When JB2 is set ITEM 21 as 1 (DIRECT) or as 2 (TRACE BACK)

  Set JB2/A ITEM 30 as -25% and ITEM 31 as 0 (HOLD VALUE)

• When JB2 is set ITEM 21 as 3 (FIXED VALUE)

  Set JB2/A ITEM 30 as -25%, and ITEM 31 as 1 (FIXED VALUE)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 14 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check current across the terminal 2 (+) – 11 (–) 

for MV output, 1 (+) – 10 (–) for the re-transmitted out-

put.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% CAS input and adjust the re-transmit-

ted output to 0%.

2) SPAN:  Apply 100% CAS input and adjust the re-trans-

mitted output to 100%.

3) Check ZERO adjustment again with 0% CAS input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

The MAN/CAS transition response time, UP/DOWN re-
sponse time (ramp rate), retroactive time period, CAS in-
put High/Low alarm setpoints are programmable using the 
PU-2x Programming Unit.  Refer to “FRONT VIEW & PRO-
GRAMMING.”

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Содержание JB2

Страница 1: ...it inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables close to noise sources relay drive cable high fr...

Страница 2: ...IMENSIONS unit mm inch 80 3 15 50 1 97 72 2 83 107 4 21 136 5 35 3 3 13 80 3 15 20 79 60 2 36 72 2 83 7 8 31 CLAMP top bottom DIN RAIL 35mm wide 2 4 5 18 dia MTG HOLE 25 98 deep 14 M3 5 SCREW When mounting no extra space is needed between units 12 5 6 14 11 1 10 15 4 3 2 7 9 8 CONNECTION DIAGRAM MV OUTPUT 4 20mA DC RE TRANSMITTED OUTPUT 4 20mA DC MAN STATUS CONTACT RUN CONTACT POWER PU 2x MODULAR ...

Страница 3: ... P Numeric SLDBAK XXX XX MAN CAS transition response second Selectable range 0 00 to 200 00 No sliding back function with 0 00 23 P UP DOWN response mode factory set value 0 0 0 UNIFORM Constant ramp rate while the key is held down 1 1 ONE UNIFORM Normal response rate for once when the key is pressed Constant ramp rate if it is continuously held down 2 2 ACCELERATED Accelerated response when the k...

Страница 4: ...moment MODE 3 Holds a specific value preset by the Programming Unit PU 2x In this mode the output can be manipulated with external UP or DOWN commands When the MAN command contact is opened the CAS control signal is recovered with smooth transition TRANSITION FROM MAN TO CAS CONTROL MODE The JB2 increases decreases the MV output until it reaches to the same value as the CAS control signal and turn...

Страница 5: ...1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input voltage Check voltage across the terminal 7 14 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check current across the terminal 2 11 for MV output 1 10 for the re transmitted out put ADJUSTMENT PROCEDURE This unit is calibrated at the ...

Отзывы: