EM-2642  Rev.3  P. 4 / 5

Modification Code

D: No modification (writing) possible.  Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the ‘PRG’ mode.

*1. RUN contact is open (coil de-energized) while in the programming mode.

 

CAS INPUT HIGH/LOW ALARM

• Alarm Trip

The High/Low alarm trips when the CAS input signal reaches or goes beyond the respective setpoints specified with ITEM 
26/27.
[Example] Low setpoint at 0.00%
The alarm trips when the input goes below 4.00mA.

• Alarm Reset

The High/Low alarm is reset when the CAS input signal goes out of the alarm zone by 1% deadband.
[Example] Lo setpoint at 0.00%

OPERATING MODES

The alarm is reset when the input goes above 4.160mA, at 4.161mA or more.

 

CASCADE CONTROL MODE

The JB2 allows the CAS input (cascade control signal) from the PID controller to pass through at the MV output terminals.

 

MANUAL CONTROL MODE

When the external MAN command contact is closed, the JB2 turns on to manual control mode.
Actual output signal is determined by following three operation modes:
    MODE 1:   Holds the CAS control signal at the moment of the MAN command.
    MODE 2:   Goes back the preset time period and hold the CAS control signal at that moment.
    MODE 3:   Holds a specific value preset by the Programming Unit (PU-2x).
In this mode, the output can be manipulated with external UP or DOWN commands.
When the MAN command contact is opened, the CAS control signal is recovered with smooth transition.

 

TRANSITION FROM MAN TO CAS CONTROL MODE

The JB2 increases/decreases the MV output until it reaches to the same value as the CAS control signal, and turns on to CAS 
control mode.  The response time constant can be set/changed with the PU-2x.
If the external command contact is closed during the transition, the JB2 output holds the signal of this moment and turns on 
to MAN control mode.

 

JB2 ACTIONS WHEN THE POWER SUPPLY IS RECOVERED AFTER FAILURE

OPERATING MODE

BEFORE FAILURE

MAN COMMAND

STATUS AT RECOVERY

ITEM 31: 0

ITEM 31: 1

CASCADE

OFF (CAS mode)

Cascade control action

Cascade control action

ON (MAN mode) *

1

Manual control starting with the 
CAS control signal at the moment 
of failure

Manual control starting with a 
specific value preset in ITEM 30

MANUAL

OFF (CAS mode)

Cascade control action

Cascade control action

ON (MAN mode) *

1

Manual control holding the MAN 
control signal at the moment of 
failure

Manual control starting with a 
specific value preset in ITEM 30

SLIDING-BACK

OFF (CAS mode)

Cascade control action

Cascade control action

ON (MAN mode) *

1

Manual control holding the transi-
tion signal at the moment of failure

Manual control starting with a 
specific value preset in ITEM 30

*1. Approx. 0.3 seconds is required to switch from CAS to MAN when the power supply is recovered.

Содержание JB2

Страница 1: ...it inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables close to noise sources relay drive cable high fr...

Страница 2: ...IMENSIONS unit mm inch 80 3 15 50 1 97 72 2 83 107 4 21 136 5 35 3 3 13 80 3 15 20 79 60 2 36 72 2 83 7 8 31 CLAMP top bottom DIN RAIL 35mm wide 2 4 5 18 dia MTG HOLE 25 98 deep 14 M3 5 SCREW When mounting no extra space is needed between units 12 5 6 14 11 1 10 15 4 3 2 7 9 8 CONNECTION DIAGRAM MV OUTPUT 4 20mA DC RE TRANSMITTED OUTPUT 4 20mA DC MAN STATUS CONTACT RUN CONTACT POWER PU 2x MODULAR ...

Страница 3: ... P Numeric SLDBAK XXX XX MAN CAS transition response second Selectable range 0 00 to 200 00 No sliding back function with 0 00 23 P UP DOWN response mode factory set value 0 0 0 UNIFORM Constant ramp rate while the key is held down 1 1 ONE UNIFORM Normal response rate for once when the key is pressed Constant ramp rate if it is continuously held down 2 2 ACCELERATED Accelerated response when the k...

Страница 4: ...moment MODE 3 Holds a specific value preset by the Programming Unit PU 2x In this mode the output can be manipulated with external UP or DOWN commands When the MAN command contact is opened the CAS control signal is recovered with smooth transition TRANSITION FROM MAN TO CAS CONTROL MODE The JB2 increases decreases the MV output until it reaches to the same value as the CAS control signal and turn...

Страница 5: ...1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input voltage Check voltage across the terminal 7 14 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check current across the terminal 2 11 for MV output 1 10 for the re transmitted out put ADJUSTMENT PROCEDURE This unit is calibrated at the ...

Отзывы: