BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner
(body + base input resistor)..................................(1)
Input resistor is provided only with current input type.

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when you 
use this product, including installation, connection, hard-
ware setting, operation of the Programming Unit (model: 
PU-2x)* specific to this model and basic maintenance pro-
cedures.
This unit is factory adjusted and calibrated according to the 
Ordering Information included in the product package.  If 
you don’t need to change the pre-adjusted setting, you can 
skip the sections on hardware setting and calibration and 
Software Setting in this manual.
* When you need to change software settings, please refer to 

the Operation Manual for Model PU-2x (EM-9255), Section B: 
(B-1) Introduction, (B-2) General Operation Description, (B-3) 
Operation Flow chart for general information.

POINTS OF CAUTION

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    100 – 240V AC rating: 85 – 264V, 47 – 66 Hz,
     

 

 

 

       approx. 4.1VA at 100V AC

     

 

 

 

       approx. 5.9VA at 200V AC

     

 

 

 

       approx. 7.7VA at 264V AC

    12 and 24V DC ratings: Rating ±10%, approx. 2.8W
    110V DC rating: 85 – 150V DC, approx. 2.8W

 

GENERAL PRECAUTIONS

• Before you remove the unit from its base socket or mount 

it, turn off the power supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C 

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

Body

Base Socket

Connection Diagram

Front Cover

Specifications

Input Resistor

 

HOW TO OPEN THE FRONT COVER:

Hang your finger on the hook at the top of the front cover 
and pull.

The shape of base socket may be different
for some models. 

 

FRONT PANEL CONFIGURATION

Output Voltage Adj.

*

Output Monitor LED B

Modular Jack

Zero Adj.

Span Adj.

Monitor LED (no function)

*

only for voltage pulse output

Output Monitor LED A

Note:  The output voltage is already adjusted according to the 

ordering information sheet.  Do NOT change the Output 
Voltage .