R7I4DECT-1-YVF4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7779-K P. 4 / 10
PC CONFIGURATOR
The following parameter items can be configured with the PC configurator software (model: R7CFG).
Refer to the users manual of the software for detailed operations.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RANGE
DEFAULT
Unused setting
CH enable,
CH disable
CH enable
Output range
-10 to +10V DC
-5 to +5V DC
-1 to +1V DC
0 to 10V DC
0 to 5V DC
1 to 5V DC
0 to 1V DC
-0.5 to +0.5V DC
-10 to +10V
DC
Bias setting
-320.00 to +320.00
(%)
0.00 (%)
Gain setting
-3.2000 to +3.2000
1.0000
Zero scaling value
-32,000 to +32,000
0
Full scaling value
-32,000 to +32,000
10,000
Output reset value*1 -15.00 to +115.00 (%)
-15.00 (%)
■
CHANNEL BATCH SETTING
PARAMETER
SETTING RANGE
DEFAULT
Output at communi-
cation error
Output hold
Output clear
Output hold
MOUNTING INSTRUCTIONS
■
DIN RAIL MOUNTING (PARALLEL)
• Mounting the unit
1) Hook the upper hook at the rear side of the base onto the
DIN rail.
2) Push the lower part of the unit in the direction of the ar-
row until the base is firmly fixed to the DIN rail.
1
2
• Removing the unit
1) Push down the slider using a minus screwdriver.
2) Pull out the lower part of the unit.
3) Remove the upper part of the unit from the DIN rail.
3
1
2
■
WALL MOUNTING
1) Insert the two DIN rail mounter sliders until they click
once, as shown below.
1
1
2) Mount the unit with M4 screws referring to the “MOUNT-
ING REQUIREMENTS unit: mm (inch)” on page 6.
(Torque: 1.4 N∙m)