manualshive.com logo in svg
background image

18JM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-1865  Rev.7  P. 3 / 5

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage supplied to the rack 

(model: 18BXx or 18KBXx).  For the DC power source, be 

sure that the ripple level is within 10% p-p.

3) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory with the total resist-
ance input, therefore you do not need any calibration if you 
use the potentiometer’s total resistance.
When you do not use the total resistance or in case of regu-
lar calibration, adjust the output as explained in the follow-
ing.   Zero and span are adjusted with using the Program-
ming Unit (model: PU-2x).
Refer to the Operation Manual for Model PU-2x for expla-
nations how to use the programmer.

 

WARNING ON USE OF THE PROGRAMMING UNIT

• Be sure to disconnect the Programming Unit before you 

turn on/off power supply to the unit.

• The output signal is held when the Programming Unit is 

connected.  You need to disconnect when confirming cur-
rent output values.

 

HOW TO CALIBRATE THE OUTPUT 1

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
There is no need of adjusting the Output 2.

• Calibrating the Output Range Proportionally to the Ac-

tual Input Resistance Range

The output range can be calibrated for input ranges nar-
rower than the total resistance, to match the actual input 
resistance range, by using the linearization table (ITEM 60 
through 91) to compensate unused resistance ranges (See 
the following figures).
If upper and lower overranges need not to be considered, 
only two calibration points will suffice.

X(02)

X(01)

0%

Y(02)

100%

Y(01)

OUTPUT

INPUT

(a), (c) : Unused Resistance

= (Total Resistance – Input Resistance)
(b) : Input Resistance

= Actual Resistance Range

100%

(a)

(b)

(c)

Figure 1. Unused Resistance

X(02)

X(01)

0%

100%

Y(02)

Y(01)

OUTPUT

INPUT

(b)

(b) : Input Resistance

= Actual Resistance Range

Figure 2. Example of Linearization

1) Confirm actual lower-range and upper-range resistance 

in percentage against the total resistance range 0 – 100%.

   In order to do this, provide actual resistance values and 

confirm them on the Programming Unit (ITEM 05: Input 
Status Monitor in %).

2) Turn the unit into Program mode (ITEM 01).
3) Enable use of the linearization table (ITEM 10: Pm-2: 

curved).

4) Set the lower-range input in % at ITEM 60.
5) Set the lower-range output in %, usually ‘0’ (zero), at 

ITEM 61.

6) Set the upper-range input in % at ITEM 62.
7) Set the upper-range output in %, usually ‘100’, at ITEM 

63.

Table 1 shows an example of settings when you need to use 
10 – 90% of the total resistance and calibrate this range to 
0 – 100%.

Table 1. Setting Example

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DATA EXAMPLE

01

S

1

MTSW : PRG. MODE

60

P

10.00

X (01) :   10.00

61

P

0.00

Y (01) :     0.00

62

P

90.00

X (02) :   90.00

63

P

100.00

Y (02) : 100.00

Modification Code

S: Modifiable at any time.
P:  Modifiable only when the MAINTENANCE SWITCH is in 

the “PRG” mode.

Отзывы: