PROGRAMMABLE ITEMS

The following items can be monitored and programmed.  For detailed explanations, please refer to the Operation Manual for 
Model PU-2x (EM-9255), Section A.

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

01

S

MAINTENANCE SWITCH (lock command)

0

MTSW: MON.MODE

MONITOR mode: data monitoring only

1

MTSW: PRG.MODE

PROGRAM mode: “P” marked data modifiable

02

P

Alphabets & No.

TG: XXXXXXXXXX

Tag name entry (10 characters max.)

03
05

P

D

Number (%)
No input

OUTPER XXX.XX
INPPER XXX.XX

Output status monitor (%) & simulation output
Input status monitor (%)

10

P

LINEARIZATION

41

Pm-1: straight

Without

42

Pm-2: curved

With (ITEM 60 to 91 for data input)

19

P

Percentage

FINZER

Fine zero adjustment
Initial status shows actual bias (%).
When data is entered, output (%) is shown.

20

P

Percentage

FINSPN

Fine span adjustment
Initial status shows actual gain (%).
When data is entered, output (%) is shown.

LINEARIZATION TABLE

60
61

P
P

Percentage
Percentage

X (01) : XXX.XX
Y (01) : XXX.XX

Input 1
Output 1

:
:

91

:
:

P

       :
       :
Percentage

       :
       :
Y (16) : XXX.XX

       :
       :
Output 16

Modification Code

D: No modification (writing) possible.  Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.