background image

3

Installation

In order to install the LUT in accordance with national/local code requirements, a qualified electrician 
should review & understand the installation instructions.  Check voltage & current requirements.  
Verify & lock out circuit breakers on both regular (utility) power & 24 hour emergency generator or 
inverter circuit.  Install a self-adhesive 2" x 3" caution label in each fixture or load controlled by an LUT 
cautioning that the load is supplied from 2 different power sources, normal & emergency.  Review 
wiring diagram & connect wires, one at a time, in accordance with the numeric identification.  In order 
to provide a safe light level, when regular power is interrupted, it is recommended that a minimum of 
appproximately 5000 lumen are controlled by a 24 hour emergency circuit & are spaced no farther 
than 24' in any direction from each other in a normal 9' white ceiling environment.

Initial Testing and Troubleshooting

In a new installation, where hundreds of devices may be used, each having as many as 14 wires to 
be correctly connected, it is important that a fast, convenient method is used to check connections.  
In order to test that the wires are connected correctly, without any inconvenience to occupants, do 
not turn off regular (utility) power off until you have checked each device as follows:

1)  Check that regular branch circuit breaker is connected & utility power is available.  Green LED 
should be lit.  If green LED is not lit, check connections & continuity to branch circuit breaker. 
2)  Check that emergency branch circuit breaker is connected & emergency power is available. 
3)  Normal Operation Test:  Turn switch or other control device to the “ON” position.  Emergency 
light should turn on.  Turn room switch or control to the “OFF” position.  Emergency light should turn 
off.
4)  Emergency Operation Test:  Press and hold test button, emergency light should illuminate at full 
brightness until test button is released.

Maintenance

No maintenance is required to keep the LUT functional.  However, regular testing should be 
performed when the lamps or ballasts have been replaced or when remodeling has taken place.  

Single Line Drawings

















Normal/Utility 
Power Source

Emergency 

Power Source

Neutral 

Not Shown





One LUT is suggested per emergency fixture.

DESIGNATED 

EMERGENCY 

LIGHT

EMERGENCY 

SHUNT 

RELAY

LIGHTING CONTROL 

DEVICE (SWITCH, 
SENSOR, POWER 

PACK, RELAY PANEL)

NORMAL

POWER

PANEL

EMERGENCY 

POWER

PANEL

UL 1008

Transfer 

Switch Or 

Equivalent

EMERGENCY 

SHUNT RELAY

EMERGENCY 

SHUNT RELAY

Содержание LUT-SHUNT-FM

Страница 1: ... This product can be used with LED ballast tungsten and general use loads 2 Make sure all connections are in accordance with the National Electrical Code and local regulations 3 To reduce the risk of electric shock disconnect both normal and emergency power supplies before servicing 4 This product is intended to be used to control indoor and outdoor located loads 5 An unswitched AC power source is...

Страница 2: ...d emergency light on and off During a utility power interruption the LUT SHUNT FM turns designated emergency light on regardless of switch position Intended for use with switching and line voltage dimming controls What is the difference between a SHUNT and an ALCR An emergency shunt relay requires a dedicated switch dimmer to control the emergency lights In other words the switch dimmer must be wi...

Страница 3: ...hat the wires are connected correctly without any inconvenience to occupants do not turn off regular utility power off until you have checked each device as follows 1 Check that regular branch circuit breaker is connected utility power is available Green LED should be lit If green LED is not lit check connections continuity to branch circuit breaker 2 Check that emergency branch circuit breaker is...

Страница 4: ... such as Philips SR XI040C110V054VPT1 and XI075C200V054VPT1 and Osram Dexal tm OTi50 120 277 1A4 DX L and OTi30 120 277 1A0 DX L 3 BROWN TEST UTILITY POWER 5 YELLOW 4 BLUE EMERGENCY PANEL OR INVERTER EMERGENCY NEUTRAL EMERGENCY LIGHT EMERGENCY HOT NORMAL UTILITY PANEL NORMAL NEUTRAL NORMAL HOT 20A 20A 2 WHITE 1 BLACK Lutron Vive Integral Fixture Control CAP OFF Wiring Diagram 3 For use with Lutron...

Отзывы: