LBV-Venting
Apply RTV sealant to the appliance vent pipe and slide over
exhaust pipe.
Secure using the four self tapping screws provided.
Slide unit into the opening, taking care not to damage the
liner (allow enough slack for final surround assembly).
Note: Inspect vent connection prior to installing
trim surrounds.
At the top of the chimney slide the connector plate over the flex liner.
Attach the termination cap to the flex pipe using the four screws
provided. Finally seal the connector plate to the chimney
(fire cement).
WARNING: Failure to position the parts in accordance with these
diagrams or failure to use only parts specifically approved with this
appliance may result in property damage or personal injury.”
Vent Installation:
IMPORTANT:
This appliances venting system requires room air for combustion, which
means that there should be provision to allow room air to be used in the combustion
process. The drafthood shall be installed so as to be in the same atmospheric
pressure zone as the combustion air inlet to the appliance. Draft openings must not be
covered or blocked.
Note:
Only UL Listed Aluminum (exhaust) 4” flex or listed ‘B’ vent pipe
may be used with the model Luxor.
The minimum venting required on the gravity vented models for safe operations is 11
feet above the appliance base with one-foot horizontal offset (with 90 degree elbows.)
PLANNING YOUR VENT INSTALLATION
When calculating the length of the vent pipe from the outlet of the appliance to
termination, allow for any offsets in the chase and sufficient vertical height above the
roof.