4     SZ-IO Control Interface Installation and Operation

Lutron Electronics Co., Inc.

Made and printed in U.S.A.

P/N 040-243 Rev. B  11.09.09

Operation

The SZ-IO receives its operating settings during 

system startup. A device database containing 

settings is transferred to the SZ-IO after it has been 

addressed. This database includes settings for:

• CCO behavior (maintained vs. momentary)

• Momentary pulse time

• CCI programming action

• System presets

LED Feedback

The SZ-IO provides 7 LEDs for user feedback:

Status LEDs

LEDs 1 through 5 provide feedback for the CCOs 

and CCIs. The display mode (CCO vs. CCI status) 

depends on the position of DIP switch 7: The LED 

lights when the CCO is active or when the CCI is 

closed.

         Switch up (on): CCI status displayed
         Switch down (off): CCO status displayed

Addressing Mode LED

LED 6 will blink during addressing. A slow blink 

(on for 3 seconds every 4 seconds) indicates an 

unaddressed device. A fast blink (once per second) 

indicates an addressed device. When not in 

addressing mode, this LED is off.

RF Link Activity LED

LED 7 will blink when the SZ-IO receives or transmits 

an RF packet.

Diagnostic Mode and  
DIP Switch Settings

Diagnostic mode allows the user to override the 

contact closure outputs (CCOs) of the device.

Diagnostic Mode Operation

1.  

Enter diagnostic mode.

 Move DIP switch 6 to the on 

(up) position. LEDs 6 and 7 will flash together (once 

per second) while the unit is in diagnostic mode.

2.  

Select CCOs to override.

 Use DIP switches 1 

through 5 to select which CCOs to close when the 

addressing (ADDR) button is pressed. (The DIP 

switch number corresponds to the CCO it controls.)

3.  

Activate the CCOs.

 Press the addressing button to 

activate the CCOs you set using the DIP switches 

in the previous step. The CCOs will remain active as 

long as the button is pressed.

4.  

Exit diagnostic mode.

 Move DIP switch 6 to the 

off (down) position. LEDs 6 and 7 will stop flashing 

together. 

Note: Diagnostic mode will exit automatically after 5 

minutes of inactivity. Pressing the addressing button 

will reset the inactivity time and the unit will remain in 

diagnostic mode.

DIP Switch Settings

Switch # 

 

LED Display 

  6  7 

Mode 

Shows

     

Normal 

Outputs

     

Normal 

Inputs

     

Diagnostic 

Outputs

     

Diagnostic 

Inputs

    Switch up (On)

    Switch down (Off)

Note:  In diagnostic mode, DIP switches 1–5 set the 

override state of the outputs.

Internet:

  www.lutron.com/stanza

e-mail:

 [email protected]

Technical support:

  USA, Canada, Caribbean: 1.800.523.9466 

Mexico: +1.888.235.2910 

Central/South America: +1.610.282.6701

Warranty:

 1-year limited warranty standard. 2-year parts and labor warranty, with 

8-year pro-rated parts replacement on systems that include factory startup.
For complete warranty details, see the Start-Up/Warranty document provided with 

your 

Stanza

 system specification submittal information.

These products may be covered under one or more of the following U.S. patents: 

5,838,226; 5,848,054; 5,905,442; 6,687,487; 6,803,728; and corresponding foreign 

patents. U.S. and foreign patents pending. Lutron and the sunburst logo are 

registered trademarks and Stanza is a trademark of Lutron Electronics Co., Inc.

© 2009 Lutron Electronics Co., Inc.

Содержание Stanza

Страница 1: ... or Chassis Ground for ESD protection see wiring diagram Wall Control interface Dimensions Dimensions are in inches mm 2 50 63 5 3 75 95 3 4 26 108 2 6 0 152 4 5 26 133 6 Mounting holes 1 06 26 9 Terminal blocks on this side LEDs and DIP switches on this side 0 23 5 8 0 31 7 9 dia 0 18 4 6 dia 6 M3 screw recommended not included Mounting Hole Detail FCC Information Note This equipment has been tes...

Страница 2: ...face to external device Output current on CCO terminals is rated as follows Low Voltage PELV Class 2 USA Wiring 1 2 3 4 5 6 7 SZ IO Front View LED 1 CCI O 1 status LED 2 CCI O 2 status LED 3 CCI O 3 status LED 4 CCI O 4 status LED 5 CCI O 5 status LED 6 Addressing mode LED 7 RF link activity CCI and CCO terminals each hold one 28 16 AWG 0 08 1 5 mm2 wire PWR COM 15 24 V 200 mA Power terminals each...

Страница 3: ...tronic drive unit EDU N C 24 V COM Wiring to from Equipment by Others PWR COM Common Available CCIs SZ IO Rear View Available CCOs From CCO equipment by others For powering equipment by others 15 24 V 100 mA max Available CCOs any available CCO can be used Note When wiring to Lutron contact closure shade as shown power is provided to the SZ IO by the window treatment power supply In this case a se...

Страница 4: ...itches 1 through 5 to select which CCOs to close when the addressing ADDR button is pressed The DIP switch number corresponds to the CCO it controls 3 Activate the CCOs Press the addressing button to activate the CCOs you set using the DIP switches in the previous step The CCOs will remain active as long as the button is pressed 4 Exit diagnostic mode Move DIP switch 6 to the off down position LED...

Страница 5: ...da 7 El SZ IO sean accesibles después de la puesta 8 El SZ IO debe estar conectado al toma a tierra o chasis a tierra para la protección ESD véase el diagrama de cableado Pared Interfaz de control Dimensiones Todas las dimensiones están en mm 63 5 95 3 108 2 152 4 133 6 Orificios de montaje 26 9 Bloque de bornes de este lado LEDs e interruptores DIP de este lado 5 8 mm 7 9 mm de Diám 4 6 mm de Diá...

Страница 6: ...sta el dispositivo externo La corriente de salida en los bornes CCO tiene los valores nominales siguientes Cableado de Bajo Voltaje PELV Clase 2 E U A 1 2 3 4 5 6 7 Vista Frontal SZ IO LED 1 CCI O 1 estado LED 2 CCI O 2 estado LED 3 CCI O 3 estado LED 4 CCI O 4 estado LED 5 CCI O 5 estado LED 6 Modo direccionado LED 7 Actividad de enlace RF PWR COM 15 24 V 200 mA Los bornes de alimentación aceptan...

Страница 7: ... de cortinas de cierre de contacto de Lutron N C 24 V COM Cableado de a equipos de otros PWR COM Común CCIs disponibles Vista posterior SZ IO CCOs disponibles Desde equipos CCO de otros Para alimentar los equipos de otros 15 24 V 100 mA máx CCOs disponibles puede usarse cualquier CCO disponible NOTA Cuando se cablea la cortina de cierre de contacto de Lutron como se muestra la alimentación es sumi...

Страница 8: ... CCOs a sobrecontrolar Use los interruptores DIP 1 a 5 para seleccionar los CCOs a cerrar cuando el botón de asignación de direcciones ADDR es presionado El número del interruptor DIP corresponde al CCO que controla 3 Active los CCOs Presione el botón de asignar direcciones para activar los CCOs que determine usando los interruptores DIP en el paso anterior Los CCOs permanecerán activos mientras e...

Страница 9: ...e exécution RF 7 Le SZ IO doit rester accessible après mise en service 8 Le SZ IO doit être relié à la terre châssis au sol ou au sol pour la protection ESD voir le schéma de câblage Mur Interface de commande Dimensions Les dimensions sont en mm 63 5 95 3 108 2 152 4 133 6 Trous de montage 26 9 Bornes de connexion de ce côté DELs et interrupteurs DIP de ce côté 5 8 mm dia 7 9 mm dia 4 6 mm Vis rec...

Страница 10: ...um entre interface et un appareil externe Le courant de sortie des bornes CCO est calibré comme suit Câblage basse tension PELV Classe 2 USA 1 2 3 4 5 6 7 Vue frontale SZ IO DEL 1 CCI O statut 1 DEL 2 CCI O statut 2 DEL 3 CCI O statut 3 DEL 4 CCI O statut 4 DEL 5 CCI O statut 5 DEL 6 Mode d adressage DEL 7 Lien d activité RF Chaque borne CCI et CCO accepte un fil 0 08 1 5 mm2 28 16 AWG PWR COM 15 ...

Страница 11: ...art d autres équipements PWR COM Commun Disponibilité des CCIs Vue arrière SZ IO Disponibilité des CCOs Provenant d autres équipements CCO Pour l alimentation d autres équipements 15 24 V 100 mA max Disponibilité des CCOs tout CCO disponible peut être utilisé Remarque lors du câblage du contact de fermeture du store Lutron l alimentation est fournie au SZ IO par le bloc d alimentation de la gestio...

Страница 12: ...s CCOs sont à fermer lorsque le bouton d adressage est enfoncé ADDR Le numéro de l interrupteur DIP correspond au CCO qu il contrôle 3 Activer les CCOs Appuyer sur le bouton d adressage pour activer les CCOs que vous réglez utilisant les interrupteurs DIP de l étape précédente Les CCOs demeurent actives aussi longtemps que le bouton est enfoncé 4 Sortir du mode diagnostic Placer l interrupteur DIP...

Отзывы: