2     SZ-IO Control Interface Installation and Operation

Contact Closure Ratings

Five Input Terminals:

• Accept maintained inputs or momentary inputs with 

40 msec minimum pulse times.

• Off-state leakage current must be less than 100 µA.

• Open circuit voltage: 24 V  maximum.

• Inputs must be dry contact closure, solid state, 

open collector, or active-low (NPN)/active high (PNP) 

output.

  -  Open collector NPN or active-low on-state voltage 

must be less than 2 V  and sink 3.0 mA.

  -  Open collector PNP or active-high on-state voltage 

must be greater than 12 V  and source 3.0 mA.

• 250 ft (76 m) maximum from external device to 

interface

Five Output Terminals:

• Provide maintained or momentary (programmable 

0.25- to 10-second) outputs.

• The SZ-IO is not rated to control unclamped, 

inductive loads. Inductive loads include, but are not 

limited to, relays, solenoids, and motors. To control 

these types of equipment, a flyback diode must be 

used (DC voltages only). See Inductive Load Wiring 

Diagram.

• Relays are non-latching and de-energize if power is 

lost.

• 250 ft (76 m) maximum from interface to external 

device.

• Output current on CCO terminals is rated as follows:

 

Low-Voltage PELV (Class 2: USA) Wiring

1 2 3 4 5 6 7

SZ-IO Front View

LED 1: CCI/O 1 status

LED 2: CCI/O 2 status

LED 3: CCI/O 3 status

LED 4: CCI/O 4 status

LED 5: CCI/O 5 status

LED 6: Addressing mode

LED 7: RF link activity

CCI and CCO terminals each hold one 

28 – 16 AWG (0.08 – 1.5 mm

2

) wire

+PWR/COM  

15 – 24 V

  200 mA 

Power terminals each 

accept two 18 AWG  

(1.0 mm

2

) wires

CCO 

NC

CCO 

NO

1-2 

COM

CCO

 2 

NC

CCO 

NO

CCO

 3 

NC

CCO 

NO

3-4 

COM

CCO

 4 

NC

CCO 

NO

CCO

 5 

NC

CCO 

NO

COM

CCI 

1

CCI 

2

CCI 

3

CCI 

4

CCI

 5

COM

+PWR COM

Wiring Diagram

PELV  

(Class 2: USA) 

Power In

15 – 24 V

200 mA

Addressing button

DIP Switches

Antenna

Contact Closure Outputs (CCO)

Contact Closure Inputs (CCI)

+

-

DC

Inductive 

Load

Flyback 

Diode

SZ-IO Output

Voltage

across CCO

0 – 24 V

0 – 24 V

R

NO

NC

Max. CCO 

Resistive 

Load

1.0 A each

0.5 A each

SZ-IO Rear View

Inductive Load Wiring Diagram

GND

 

N/C

NOTE:

 Device should be powered using 

the supplied transformer or shade power 

supply (Lutron P/N: SZ-PS-P1-1-50). See 

wiring diagram. Contact tech support 

prior to powering device using any other 

transformer or power supply.

NOTE:

 For ESD 

protection, ground wire 

should be connected 

to Earth/Ground before 

device is powered.

Содержание Stanza

Страница 1: ... or Chassis Ground for ESD protection see wiring diagram Wall Control interface Dimensions Dimensions are in inches mm 2 50 63 5 3 75 95 3 4 26 108 2 6 0 152 4 5 26 133 6 Mounting holes 1 06 26 9 Terminal blocks on this side LEDs and DIP switches on this side 0 23 5 8 0 31 7 9 dia 0 18 4 6 dia 6 M3 screw recommended not included Mounting Hole Detail FCC Information Note This equipment has been tes...

Страница 2: ...face to external device Output current on CCO terminals is rated as follows Low Voltage PELV Class 2 USA Wiring 1 2 3 4 5 6 7 SZ IO Front View LED 1 CCI O 1 status LED 2 CCI O 2 status LED 3 CCI O 3 status LED 4 CCI O 4 status LED 5 CCI O 5 status LED 6 Addressing mode LED 7 RF link activity CCI and CCO terminals each hold one 28 16 AWG 0 08 1 5 mm2 wire PWR COM 15 24 V 200 mA Power terminals each...

Страница 3: ...tronic drive unit EDU N C 24 V COM Wiring to from Equipment by Others PWR COM Common Available CCIs SZ IO Rear View Available CCOs From CCO equipment by others For powering equipment by others 15 24 V 100 mA max Available CCOs any available CCO can be used Note When wiring to Lutron contact closure shade as shown power is provided to the SZ IO by the window treatment power supply In this case a se...

Страница 4: ...itches 1 through 5 to select which CCOs to close when the addressing ADDR button is pressed The DIP switch number corresponds to the CCO it controls 3 Activate the CCOs Press the addressing button to activate the CCOs you set using the DIP switches in the previous step The CCOs will remain active as long as the button is pressed 4 Exit diagnostic mode Move DIP switch 6 to the off down position LED...

Страница 5: ...da 7 El SZ IO sean accesibles después de la puesta 8 El SZ IO debe estar conectado al toma a tierra o chasis a tierra para la protección ESD véase el diagrama de cableado Pared Interfaz de control Dimensiones Todas las dimensiones están en mm 63 5 95 3 108 2 152 4 133 6 Orificios de montaje 26 9 Bloque de bornes de este lado LEDs e interruptores DIP de este lado 5 8 mm 7 9 mm de Diám 4 6 mm de Diá...

Страница 6: ...sta el dispositivo externo La corriente de salida en los bornes CCO tiene los valores nominales siguientes Cableado de Bajo Voltaje PELV Clase 2 E U A 1 2 3 4 5 6 7 Vista Frontal SZ IO LED 1 CCI O 1 estado LED 2 CCI O 2 estado LED 3 CCI O 3 estado LED 4 CCI O 4 estado LED 5 CCI O 5 estado LED 6 Modo direccionado LED 7 Actividad de enlace RF PWR COM 15 24 V 200 mA Los bornes de alimentación aceptan...

Страница 7: ... de cortinas de cierre de contacto de Lutron N C 24 V COM Cableado de a equipos de otros PWR COM Común CCIs disponibles Vista posterior SZ IO CCOs disponibles Desde equipos CCO de otros Para alimentar los equipos de otros 15 24 V 100 mA máx CCOs disponibles puede usarse cualquier CCO disponible NOTA Cuando se cablea la cortina de cierre de contacto de Lutron como se muestra la alimentación es sumi...

Страница 8: ... CCOs a sobrecontrolar Use los interruptores DIP 1 a 5 para seleccionar los CCOs a cerrar cuando el botón de asignación de direcciones ADDR es presionado El número del interruptor DIP corresponde al CCO que controla 3 Active los CCOs Presione el botón de asignar direcciones para activar los CCOs que determine usando los interruptores DIP en el paso anterior Los CCOs permanecerán activos mientras e...

Страница 9: ...e exécution RF 7 Le SZ IO doit rester accessible après mise en service 8 Le SZ IO doit être relié à la terre châssis au sol ou au sol pour la protection ESD voir le schéma de câblage Mur Interface de commande Dimensions Les dimensions sont en mm 63 5 95 3 108 2 152 4 133 6 Trous de montage 26 9 Bornes de connexion de ce côté DELs et interrupteurs DIP de ce côté 5 8 mm dia 7 9 mm dia 4 6 mm Vis rec...

Страница 10: ...um entre interface et un appareil externe Le courant de sortie des bornes CCO est calibré comme suit Câblage basse tension PELV Classe 2 USA 1 2 3 4 5 6 7 Vue frontale SZ IO DEL 1 CCI O statut 1 DEL 2 CCI O statut 2 DEL 3 CCI O statut 3 DEL 4 CCI O statut 4 DEL 5 CCI O statut 5 DEL 6 Mode d adressage DEL 7 Lien d activité RF Chaque borne CCI et CCO accepte un fil 0 08 1 5 mm2 28 16 AWG PWR COM 15 ...

Страница 11: ...art d autres équipements PWR COM Commun Disponibilité des CCIs Vue arrière SZ IO Disponibilité des CCOs Provenant d autres équipements CCO Pour l alimentation d autres équipements 15 24 V 100 mA max Disponibilité des CCOs tout CCO disponible peut être utilisé Remarque lors du câblage du contact de fermeture du store Lutron l alimentation est fournie au SZ IO par le bloc d alimentation de la gestio...

Страница 12: ...s CCOs sont à fermer lorsque le bouton d adressage est enfoncé ADDR Le numéro de l interrupteur DIP correspond au CCO qu il contrôle 3 Activer les CCOs Appuyer sur le bouton d adressage pour activer les CCOs que vous réglez utilisant les interrupteurs DIP de l étape précédente Les CCOs demeurent actives aussi longtemps que le bouton est enfoncé 4 Sortir du mode diagnostic Placer l interrupteur DIP...

Отзывы: