GRAFIK Eye
®
QS with DALI Quick Installation and Operation Guide 3
For additional information, see the complete installation and operation guide at
www.lutron.com/qs
Wiring the GRAFIK Eye
®
QS with DALI:
Overview of Line Voltage/Mains and DALI Wiring
4,0 mm
2
(12 AWG)
each terminal
100 – 240 V
50 / 60 Hz
Distribution
Panel
Line Voltage/Mains
Cables and Load Wiring
D2
D1
D2
D1
To additional DALI
devices
DALI Bus Wiring
(See page 5 for complete wiring
specification)
Two 1,5 mm
2
(16 AWG)
each terminal
DALI devices: ballasts,
drivers, or interfaces
Two D1 and two D2 connections are
provided for ease of wiring, and to
provide two connecting points; there is
only one DALI link on the unit.
Note:
Ballasts and other DALI devices
must
NOT
obtain power from a line
voltage output on the
GRAFIK Eye
QS
with DALI
.
Distribution
Panel
L
N
L
N
Terminal labels:
L: Hot/Live
N: Neutral
: Ground