5.
Verify that the Receiver button has learned the
Transmitter button by pressing the Transmitter
button again. The orange LED corresponding to
the learned button on the Receiver will flash. The
LEARN LED will also flash.
6.
Repeat steps 3 and 4 to learn additional
Transmitter buttons.
7.
Exit LEARN Mode. Press and release the LEARN
button.
The green LEARN LED
turns OFF.
Operation
3
English
Français
Esp
añol
Português
Contact Closure
Outputs
Provide a contact
closure output for
as long as the but-
ton is pressed.
Programmable
Buttons
Button functions
are programmed
using the
HomeWorks
®
Utility.
LEARN Button
Used to enter
LEARN Mode.
LEARN Mode is
used when the
Receiver is learn-
ing Transmitter
buttons.
Resistive
Inductive
Voltage
Load
Load
Up to 30 VDC
1 A
0.2 A
Up to 30 VAC
1 A
0.1 A
Up to 60 VDC
0.5 A
Do not use
Up to 42.4 VAC
0.5 A
Do not use
Wiring Diagram
Relay Contact Ratings
Third-party equipment
contact closure input.
CCO 1
CCO 2
CCO 3
CCO 4