Lutron Electronics Energi Savr Node QS QSNE-4S10-D Скачать руководство пользователя страница 7

Energi Savr Node

TM

 QS | Programming Guide

Energi Savr Node

TM

 QS 

|

 Programming Guide

Lutron

®

  

|

  7

QSE-IO Association - Scene DIP configuration

The 

Energi Savr Node

 QS unit can be associated to a QSE-IO (contact closure interface) that is set in a Scene 

DIP configuration. This can be used to change scenes on your 

Energi Savr Node

 QS unit from third party 

equipment (using contact closure inputs into the QSE-IO), or to monitor scene changes on your 

Energi Savr 

Node

 QS unit from third party equipment (using contact closure outputs out of the QSE-IO). Consult the QSE-

IO instructions for proper DIP configuration.
To associate a QSE-IO that is set in a Scene DIP configuration to an 

Energi Savr Node

 QS unit(s), follow the 

steps below:

1. Press and hold the 

Program

 button on the QSE-IO for 3 seconds to enter Programming Mode. The 5 output 

LEDs will cycle. The sensor Group A and Group B LEDs and the ‘H’, ‘M’ and ‘L’ LEDs on the 

Energi Savr Node

 

QS unit(s) will flash sequentially in groups.

2. To assign desired zone(s) to the QSE-IO, press and hold the 

Zone

 button on the 

Energi Savr Node

 QS unit for 

each desired zone for 3 seconds. A blinking ‘Zone’ LED indicates an assigned zone.

3. To exit Programming Mode, press and hold the 

Program

 button on the QSE-IO for 3 seconds.

To un-assign zones from the QSE-IO, press and hold the 

Zone

 button on the 

Energi Savr Node

 QS unit for 3 

seconds. The ‘Zone’ LED will turn off to indicate success.
Repeat for each zone that you wish to un-assign from the QSE-IO.

QSE-IO Association - Zone Toggle and Occupancy DIP configurations

The 

Energi Savr Node

 QS unit can also associated to a QSE-IO (contact closure interface) that is set in the 

Zone Toggle or Occupancy DIP configuration. In the Zone Toggle configuration, this can be used to toggle 
zones on your 

Energi Savr Node 

QS unit from third party equipment (using contact closure inputs into the 

QSE-IO), or to monitor the state (on or off) of the zones on your 

Energi Savr Node

 QS unit from third party 

equipment (using contact closure outputs out of the QSE-IO). In the Occupancy configuration, this can be 
used to associate additional occupancy sensors to the zones on your 

Energi Savr Node 

QS unit (to turn lights 

on and off based on room occupancy). Consult the QSE-IO instructions for proper DIP configuration.

To associate a QSE-IO that is set in a Zone Toggle or Occupancy DIP configuration to an 

Energi Savr Node

 QS 

unit(s), follow the steps below:

1. Press and hold the 

Program

 button on the QSE-IO for 3 seconds to enter Programming Mode. The first 

output LED will flash indicating input 1 is selected. The sensor Group A and Group B LEDs and the ‘H’, ‘M’ 
and ‘L’ LEDs on the 

Energi Savr Node

 QS unit(s) will flash sequentially in groups.

2. To assign desired zone(s) to input 1 of the QSE-IO, press and hold the 

Zone

 button on the 

Energi Savr Node

 

QS unit for each desired zone for 3 seconds. A blinking ‘Zone’ LED indicates an assigned zone.

3. Press and release the 

Program

 button on the QSE-IO to select the next input. Repeat step 2 for the remaining 

inputs on the QSE-IO. 

4. To exit Programming Mode, press and hold the 

Program

 button on the QSE-IO for 3 seconds. 

To un-assign zones from the QSE-IO inputs, press and hold the 

Zone

 button on the 

Energi Savr Node

 QS unit 

for 3 seconds. The ‘Zone’ LED will turn off to indicate success.
Repeat for each zone that you wish to un-assign from its respective QSE-IO input.

Содержание Energi Savr Node QS QSNE-4S10-D

Страница 1: ...nctionality 2 Programming 3 Input Programming Mode 3 Sensor Overview 3 Advanced Button Programming 4 Scene Programming Mode 4 QS Link Input s Setup 6 Contact Information 8 Energi Savr NodeTM QS Programming Guide Model QSNE 4S10 D ...

Страница 2: ...compatible transmitters QS Wallstations All seeTouch QS wallstations are Scene keypads by default Scenes 1 16 will turn all the lights On Scene Off will turn all the lights Off Contact Closure Input CCI The CCI behaves as an Emergency Contact Closure Input If the CCI is open the Energi Savr Node QS unit will enter Emergency Mode which will turn on all loads and disable local zone control and contr...

Страница 3: ... first unassociate any previously assigned sensors from that zone including those in out of box mode Only sensors powered directly from the Energi Savr Node QS unit will flash Sensor Overview Occupancy Sensors Energi Savr Node QS units are programmable to turn lights on and off based on room occupancy detected by compatible occupancy sensors To ensure proper operation of the Energi Savr Node QS un...

Страница 4: ...nsor Use the and buttons to select response mode H LED indicates Occupancy mode Auto on off M LED indicates Vacancy mode Manual on auto off Opt1 Set daylight sensor setpoint for each zone Use the button to increase the set point Use the button to decrease the set point 4 Repeat steps 2 and 3 for each desired zone 5 Simultaneously press and hold the Program and Input buttons for 3 seconds to exit Z...

Страница 5: ... indicated by flashing Option LEDs as shown ion the chart below LED Legend steady on flashing off LEDs Scene LEDs Scene LEDs Scene LEDs Scene Scene 5 Scene 6 Scene 7 Scene 8 Scene 9 Scene 10 Scene 11 Scene 12 Scene 13 Scene 14 Scene 15 Scene 16 3 Use the and buttons to set the selected scene to On or Off The H M and L LED group indicates your choice all LEDs on On all LEDs off Off 4 To make a zone...

Страница 6: ...ld the top and bottom buttons on the wallstation for 3 seconds The QS link enters Programming Mode The sensor Group A and Group B LEDs and the H M and L LEDs on the Energi Savr Node QS unit s will flash sequentially in groups 2 Use the Option button to change the wallstation type to zone toggle A blinking LED will indicate the selection Select Opt 2 3 To save the wallstation type press and hold th...

Страница 7: ...sociated to a QSE IO contact closure interface that is set in the Zone Toggle or Occupancy DIP configuration In the Zone Toggle configuration this can be used to toggle zones on your Energi Savr Node QS unit from third party equipment using contact closure inputs into the QSE IO or to monitor the state on or off of the zones on your Energi Savr Node QS unit from third party equipment using contact...

Страница 8: ...a Centre Singapore 089316 TEL 65 6220 4666 FAX 65 6220 4333 Technical hotlines France 0800 90 12 18 Germany 00800 5887 6635 Italy 800 979 208 Spain 900 948 944 Northern China 10 800 712 1536 Southern China 10 800 120 1536 Hong Kong 800 901 849 Singapore 800 120 4491 Taiwan 00 801 137 737 Thailand 001 800 120 665853 Other Areas in Asia 65 6220 4666 Lutron Electronics Co Inc 7200 Suter Road Coopersb...

Отзывы: