Lutron Electronics Energi Savr Node QS QSNE-4S10-D Скачать руководство пользователя страница 3

Energi Savr Node

TM

 QS | Programming Guide

Energi Savr Node

TM

 QS 

|

 Programming Guide

Lutron

®

  

|

  3

Programming

The out-of-box settings of an 

Energi Savr Node

 QS unit can be changed to customize the installation. Please 

follow the steps described below to adjust the settings on your 

Energi Savr Node

 QS unit.

Input Programming Mode

   * Note: After 10 minutes without activity on the user interface, the 

Energi Savr Node

 QS unit will automatically 

exit the Input Programming Mode. The 

Energi Savr Node

 QS unit will retain the latest changes.

Assign/Unassign zones to wired sensors

1. To enter Input Programming Mode, press and hold the 

Program

 button for 3 seconds. The ‘Program’ LED will 

blink. 

2. Press 

Program

 button to sequence through each sensor input. The LED corresponding to the selected 

sensor input will blink. If powered by the 

Energi Savr Node

 QS unit, the sensor will flash also.*

3. For each desired zone, press & hold the 

Zone

 button until the LED changes state to assign or un-assign that 

zone. A blinking ‘Zone’ LED indicates that a zone is assigned. 

4. To exit Input Programming Mode, press and hold the 

Program

 button for 3 seconds.

Note: Before assigning a daylight sensor to a zone, you must first unassociate any previously assigned sensors 
from that zone, including those in out-of-box mode.

   * Only sensors powered directly from the 

Energi Savr Node

 QS unit will flash.

Sensor Overview

Occupancy Sensors

Energi Savr Node 

QS units are programmable to turn lights on and off based on room occupancy detected by 

compatible occupancy sensors. To ensure proper operation of the 

Energi Savr Node

 QS unit:

•  Wire no more than 2 occupancy sensors to any one Occ connection. 

An auxiliary power supply must be used 

if the device(s) require(s) more than 50 mA.

Daylight Sensors

Energi Savr Node

 QS units are programmable to turn lights on and off based on daylight detected by 

compatible Lutron

®

 daylight sensors. To ensure proper operation of the 

Energi Savr Node

 QS unit:

•  Use only 

Lutron

 daylight sensors (EC-DIR-WH).

•  Only wire one sensor to a single Photo input.

Each zone output on an 

Energi Savr Node

 QS unit can be programmed to respond to a single daylight sensor. 

The target setpoint for turn-on/turn-off is adjustable for each zone—one sensor may be linked to multiple 
zones, each zone with its own unique setpoint. Please note that:

•  A daylight sensor wired to an 

Energi Savr Node

 QS unit can be assigned to control any or all zones on that 

Energi Savr Node

 QS unit.

•  Daylight sensors will not turn a zone on if an occupancy sensor assigned to that zone detects that the room is 

vacant.

Содержание Energi Savr Node QS QSNE-4S10-D

Страница 1: ...nctionality 2 Programming 3 Input Programming Mode 3 Sensor Overview 3 Advanced Button Programming 4 Scene Programming Mode 4 QS Link Input s Setup 6 Contact Information 8 Energi Savr NodeTM QS Programming Guide Model QSNE 4S10 D ...

Страница 2: ...compatible transmitters QS Wallstations All seeTouch QS wallstations are Scene keypads by default Scenes 1 16 will turn all the lights On Scene Off will turn all the lights Off Contact Closure Input CCI The CCI behaves as an Emergency Contact Closure Input If the CCI is open the Energi Savr Node QS unit will enter Emergency Mode which will turn on all loads and disable local zone control and contr...

Страница 3: ... first unassociate any previously assigned sensors from that zone including those in out of box mode Only sensors powered directly from the Energi Savr Node QS unit will flash Sensor Overview Occupancy Sensors Energi Savr Node QS units are programmable to turn lights on and off based on room occupancy detected by compatible occupancy sensors To ensure proper operation of the Energi Savr Node QS un...

Страница 4: ...nsor Use the and buttons to select response mode H LED indicates Occupancy mode Auto on off M LED indicates Vacancy mode Manual on auto off Opt1 Set daylight sensor setpoint for each zone Use the button to increase the set point Use the button to decrease the set point 4 Repeat steps 2 and 3 for each desired zone 5 Simultaneously press and hold the Program and Input buttons for 3 seconds to exit Z...

Страница 5: ... indicated by flashing Option LEDs as shown ion the chart below LED Legend steady on flashing off LEDs Scene LEDs Scene LEDs Scene LEDs Scene Scene 5 Scene 6 Scene 7 Scene 8 Scene 9 Scene 10 Scene 11 Scene 12 Scene 13 Scene 14 Scene 15 Scene 16 3 Use the and buttons to set the selected scene to On or Off The H M and L LED group indicates your choice all LEDs on On all LEDs off Off 4 To make a zone...

Страница 6: ...ld the top and bottom buttons on the wallstation for 3 seconds The QS link enters Programming Mode The sensor Group A and Group B LEDs and the H M and L LEDs on the Energi Savr Node QS unit s will flash sequentially in groups 2 Use the Option button to change the wallstation type to zone toggle A blinking LED will indicate the selection Select Opt 2 3 To save the wallstation type press and hold th...

Страница 7: ...sociated to a QSE IO contact closure interface that is set in the Zone Toggle or Occupancy DIP configuration In the Zone Toggle configuration this can be used to toggle zones on your Energi Savr Node QS unit from third party equipment using contact closure inputs into the QSE IO or to monitor the state on or off of the zones on your Energi Savr Node QS unit from third party equipment using contact...

Страница 8: ...a Centre Singapore 089316 TEL 65 6220 4666 FAX 65 6220 4333 Technical hotlines France 0800 90 12 18 Germany 00800 5887 6635 Italy 800 979 208 Spain 900 948 944 Northern China 10 800 712 1536 Southern China 10 800 120 1536 Hong Kong 800 901 849 Singapore 800 120 4491 Taiwan 00 801 137 737 Thailand 001 800 120 665853 Other Areas in Asia 65 6220 4666 Lutron Electronics Co Inc 7200 Suter Road Coopersb...

Отзывы: