Please refer to the daylight sensor installation guide for details on sensor placement.
Infrared (IR) Remote Receivers
Energi Savr Node
QS units are programmable to turn lights on and off based on signals provided by
compatible Lutron
®
IR transmitters and received by compatible
Lutron
IR receivers. To ensure proper operation
of the
Energi Savr Node
QS unit:
• Use only
Lutron
IR receivers (EC-DIR-WH, EC-IR-WH, CC-1BRL-WH, CC-4BRL-WH)
• See
Lutron
IR receiver literature for compatible IR transmitters.
• Only wire one receiver to a single IR input
Advanced Button Programming
Each
Energi Savr Node
QS unit zone has several parameters that can be set or adjusted. Follow the steps
below to adjust a zone’s setting.
Configure Zone Parameters
1. Simultaneously press and hold the
Program
and
Input
buttons for 3 seconds to enter Zone Set-up Mode.
‘Program’ and Group A LEDs will flash rapidly.
2. Press
Zone
button to select the zone for which you wish to set parameters.
3. Use the
Option
button to select a parameter to set or adjust as listed below. The option LEDs will turn on to
indicate your selection:
Option LED(s) Parameter
Method
‘Def’
Set zone to respond to wired Occupancy
sensor as either Occupancy or Vacancy
sensor
Use the
and buttons to select response mode.
· ‘H’ LED indicates Occupancy mode (Auto on/off).
· ‘M’ LED indicates Vacancy mode (Manual on/
auto off)
‘Opt1’
Set daylight sensor setpoint for each
zone
Use the
button to increase the set point.
Use the
button to decrease the set point.
4. Repeat steps 2 and 3 for each desired zone.
5. Simultaneously press and hold the
Program
and
Input
buttons for 3 seconds to exit Zone Set-up Mode.
Scene Programming Mode
Scene Programming
Each output zone on the
Energi Savr Node
QS unit has 16 scenes plus Off. Each scene can be programmed
to turn the zone on or off, or the zone can be set to be unaffected in a scene, so that changing to that scene
will not change the unaffected zone from its current level. Note: Scene Off cannot be modified.
Follow the steps below and in the QS Link Input(s) Set-up section.
Scenes 1-4
1. Simultaneously press and hold the
Program
and
Option
buttons on the
Energi Savr Node
QS unit for 3
seconds to enter Scene Programming Mode. ‘Program’ and Group B LEDs will flash rapidly.
2. Use the
Option
button to select a scene to define for each zone. Option LED will be steady on, to indicate
current scene selected:
LED Legend: = steady on = flashing = off
LEDs Scene # LEDs Scene # LEDs Scene # LEDs Scene #
Scene 1
Scene 2
Scene 3
Scene 4
3. Use the
and
buttons to set the selected scene to On or Off. The ‘H’, ‘M’, and ‘L’ LED group indicates your
choice: all LEDs on = On; all LEDs off = Off.
4. To make a zone unaffected, press and hold the button until only the ‘M’ LED turns on.