Mounting Plate Dimensions
Using the Infrared Mask
Center Ceiling Mount
(Mask blocks sensor
seeing out doorway
into hall)
Corner Ceiling Mount
(No mask needed)
Typical Mask Patterns
Conference
Room Mask
180° Mask
Full Mask
Rectangular
Areas
Over the
Door
Specific
Areas You
Wish to Mask
Normal Mounting:
Insert ACAK into mounting bracket and twist
90˚ to lock in place. Drill through ceiling tile with
assembly,using the cutter end of the threaded
mounting post. Secure with washer and nut.
Mounting to Non-Standard Ceiling/Fixture:
Drill wiring routing hole and (2) mounting holes using
Mounting Bracket as template. Secure twist-lock
cover plate using mounting screws, nuts, and
washers (included).
Auto/Manual
Threshold
LED Motion Indicator
Reset Learned Settings
Strong Airflow Compensation
Over Doorway Installation
Timer Adjust
Auto Sensitivity
1
2
3
4
Sensor Adjustments
Override Settings
1
2
3
4
B
Number of Sensors
1
2
3
1
2
1
Number of Auxiliary
Power Packs
0
0
0
1
1
2
22 AWG
750 ft
375 ft
250 ft
375 ft
250 ft
250 ft
0.5 mm
2
365 m
180 m
120 m
90 m
120 m
120 m
20 AWG
1200 ft
600 ft
400 ft
600 ft
400 ft
400 ft
0.75 mm
2
730 m
365 m
240 m
365 m
240 m
365 m
18 AWG
2400 ft
1200 ft
800 ft
1200 ft
800 ft
800 ft
Wire Lengths (when powered by power pack)
Installation and Mounting
4.2 in
(106.6 mm)
0.52 in
(13.3 mm)
2.5 in
(63 mm)
ON
OFF
Off (Default)
On
Automatic (Normal)
Manually On/Off (Override)
Auto Threshold Adjustment
High Sensitivity (Low turn-on threshold)
Lights indicate motion
Disable LED Indicator
Retain Settings (Normal)
Erase all learned settings; Restart Learning (Toggle On)
ON
OFF
Off (Default)
On
Disable Compensation (Normal)
Enable Compensation
No (Normal)
Yes (Use increased turn-on threshold)
Adjust timer Automatically
Use Manual Setting
Adjust Sensitivity Automatically
Adjust Sensitivity Manually
A
Cutter end
Pre-installation
WARNING: SHOCK HAZARD. May result in death or serious injury.
Disconnect power before servicing or installing.
1. For installation by a qualified electrician in accordance with national and local codes and the following instructions.
2. Use copper conductors only
3. Do not connect this product to line voltage/mains cable
4. For indoor use only.
5. Check to see that the device type and rating is suitable for the application.
6. Do not install if product or lens have any visible damage.
7. If moisture or condensation is evident, allow the product to dry completely before installation.
Wiring
Sensor:
Route wiring through ACAK/ceiling tile. Attach the sensor body
to the cover plate by aligning the arrows and twist locking into
place. Connect wiring with twist on connectors.
ACAK
Acoustic Ceiling
Adaptor Kit (optional)